LC1D256FLS207

RAIL SPECIAL PURPOSE CONTACTOR 3P

Trade Price

£151.45

Per

1

Unit

EA

Pack Quantity

1

LC1D256FLS207

Technical Specifications

Range

TeSys TeSys Deca

Range of product

TeSys Deca

Product or component type

Contactor

Device short name

LC1D

contactor application

Resistive load Motor control

utilisation category

AC-1 AC-3 AC-3e

Poles description

3P

[Ue] rated operational voltage

Power circuit: <= 690 V AC 25...400 Hz

[Ie] rated operational current

25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit 25 A (at <60 °C) at <= 440 V AC AC-3e for power circuit

Motor power kW

5.5 kW at 220/230 V AC 50 Hz (AC-3) 11 kW at 380/400 V AC 50 Hz (AC-3) 11 kW at 415 V AC 50 Hz (AC-3) 11 kW at 440 V AC 50 Hz (AC-3) 15 kW at 500 V AC 50 Hz (AC-3) 15 kW at 660/690 V AC 50 Hz (AC-3) 5.5 kW at 220/230 V AC 50 Hz (AC-3e) 11 kW at 380/400 V AC 50 Hz (AC-3e) 11 kW at 415 V AC 50 Hz (AC-3e) 11 kW at 440 V AC 50 Hz (AC-3e) 15 kW at 500 V AC 50 Hz (AC-3e) 15 kW at 660/690 V AC 50 Hz (AC-3e)

Pole contact composition

3 NO

Contact compatibility

M5

Protective cover

With

Auxiliary contacts type

type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1

Auxiliary contact composition

1 NO + 1 NC

[Ui] rated insulation voltage

Power circuit: 690 V conforming to IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-1

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Overvoltage category

III

[Ith] conventional free air thermal current

10 A (at 60 °C) for signalling circuit 40 A (at 60 °C) for power circuit

Irms rated making capacity

140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 450 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity

450 A at 440 V for power circuit conforming to IEC 60947

Associated fuse rating

10 A gG for signalling circuit conforming to IEC 60947-5-1 63 A gG at <= 690 V coordination type 1 for power circuit 40 A gG at <= 690 V coordination type 2 for power circuit

Time constant

37 ms

Control circuit type

DC low consumption

Coil technology

With integral suppression device

Control circuit voltage limits

0.1...0.25 Uc (-40…70 °C):drop-out DC 0.7...1.25 Uc (-40…70 °C):operational DC

Average impedance

2 mOhm - Ith 40 A 50 Hz for power circuit

Power dissipation per pole

3.2 W AC-1 1.25 W AC-3 1.25 W AC-3e

Minimum switching current

5 mA for signalling circuit

Minimum switching voltage

17 V for signalling circuit

Non-overlap time

1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact

Operating time

55...75 ms closing 16...32 ms opening

Maximum operating rate

3600 cyc/h 60 °C

Inrush power in W

4 W (at 20 °C)

Hold-in power consumption in W

4 W at 20 °C

Insulation resistance

> 10 MOhm for signalling circuit

Connections - terminals

Control circuit: lugs-ring terminals - external diameter: 8 mm Power circuit: lugs-ring terminals - external diameter: 12 mm

Tightening torque

Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5 Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5 Power circuit: 2.5 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M4 Power circuit: 2.5 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M4

mounting support

Plate Rail

Electrical durability

1.65 Mcycles 25 A AC-3 at Ue <= 440 V 1.4 Mcycles 40 A AC-1 at Ue <= 440 V 1.65 Mcycles 25 A AC-3e at Ue <= 440 V

Mechanical durability

30 Mcycles

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Operating altitude

0...3000 m

Compatibility code

LC1D

Standards

EN/IEC 60947-4-1 EN/IEC 60947-5-1 EN 45545: R22 HL3 EN 45545: R26 HL3 DIN 5510-2

product certifications

IEC CCC EAC UA TR UKCA

Climatic withstand

conforming to IACS E10 conforming to IEC 60947-1 Annex Q category D

Ambient air temperature for storage

-60…80 °C

Fire resistance

850 °C conforming to IEC 60695-2-1

height

85 mm

Width

45 mm

Depth

101 mm

Net weight

0.37 kg

Mechanical robustness

Vibrations contactor open (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz) Shocks contactor closed (15 Gn for 11 ms) Shocks contactor open (8 Gn for 11 ms)

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

12.0 cm

Package 1 Width

9.5 cm

Package 1 Length

5.4 cm

Package 1 Weight

628.0 g

Unit Type of Package 2

S02

Number of Units in Package 2

15

Package 2 Height

15.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

9.875 kg

Unit Type of Package 3

P06

Number of Units in Package 3

240

Package 3 Height

77.0 cm

Package 3 Width

80.0 cm

Package 3 Length

60.0 cm

Package 3 Weight

150.72 kg

Warranty

18 months

Document Links

Datasheet

Technical Data