Trade Price
£99.39
Per
1
Unit
EA
Pack Quantity
1
Range
TeSys TeSys Deca
Range of product
TeSys Deca
Product or component type
Contactor
Device short name
LC1D
contactor application
Resistive load Motor control
utilisation category
AC-1 AC-3 AC-3e
Poles description
3P
[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
[Ie] rated operational current
9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit 9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Motor power kW
2.2 kW at 220/230 V AC 50 Hz (AC-3) 4 kW at 380/400 V AC 50 Hz (AC-3) 4 kW at 415 V AC 50 Hz (AC-3) 4 kW at 440 V AC 50 Hz (AC-3) 5.5 kW at 500 V AC 50 Hz (AC-3) 5.5 kW at 660/690 V AC 50 Hz (AC-3) 2.2 kW at 220/230 V AC 50 Hz (AC-3e) 4 kW at 380/400 V AC 50 Hz (AC-3e) 4 kW at 415 V AC 50 Hz (AC-3e) 4 kW at 440 V AC 50 Hz (AC-3e) 5.5 kW at 500 V AC 50 Hz (AC-3e) 5.5 kW at 660/690 V AC 50 Hz (AC-3e)
Pole contact composition
3 NO
Contact compatibility
M4
Protective cover
With
Auxiliary contacts type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1
Auxiliary contact composition
1 NO + 1 NC
[Ui] rated insulation voltage
Power circuit: 690 V conforming to IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
Overvoltage category
III
[Ith] conventional free air thermal current
10 A (at 60 °C) for signalling circuit 25 A (at 60 °C) for power circuit
Irms rated making capacity
250 A at 440 V for power circuit conforming to IEC 60947 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity
250 A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1 25 A gG at <= 690 V coordination type 1 for power circuit 20 A gG at <= 690 V coordination type 2 for power circuit
Time constant
28 ms
Control circuit type
DC standard
Coil technology
With integral suppression device
Control circuit voltage limits
0.1...0.25 Uc (-40…70 °C):drop-out DC 0.7...1.25 Uc (-40…70 °C):operational DC with spacing >8 mm 0.7...1.25 Uc (-40…50 °C):operational DC 0.7...1.1 Uc (50…70 °C):operational DC
Average impedance
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Power dissipation per pole
1.56 W AC-1 0.2 W AC-3 0.2 W AC-3e
Minimum switching current
5 mA for signalling circuit
Minimum switching voltage
17 V for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
Operating time
55...75 ms closing 16...32 ms opening
Maximum operating rate
3600 cyc/h 60 °C
Inrush power in W
5.4 W (at 20 °C)
Hold-in power consumption in W
5.4 W at 20 °C
Insulation resistance
> 10 MOhm for signalling circuit
Connections - terminals
Control circuit: lugs-ring terminals - external diameter: 8 mm Power circuit: lugs-ring terminals - external diameter: 9.5 mm
Tightening torque
Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5 Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5 Power circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5 Power circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5 Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2 M3.5 Power circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2 M3.5
mounting support
Rail Plate
Electrical durability
0.6 Mcycles 25 A AC-1 at Ue <= 440 V 2 Mcycles 9 A AC-3 at Ue <= 440 V 2 Mcycles 9 A AC-3e at Ue <= 440 V
Mechanical durability
30 Mcycles
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Operating altitude
0...3000 m
Compatibility code
LC1D
Standards
EN/IEC 60947-4-1 EN/IEC 60947-5-1 EN 45545: R22 HL3 EN 45545: R26 HL3 DIN 5510-2
product certifications
IEC CCC EAC UA TR UKCA
Climatic withstand
conforming to IACS E10 conforming to IEC 60947-1 Annex Q category D
Ambient air temperature for storage
-60…80 °C
Fire resistance
850 °C conforming to IEC 60695-2-1
height
77 mm
Width
45 mm
Depth
95 mm
Net weight
0.32 kg
Mechanical robustness
Vibrations contactor open (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz) Shocks contactor open (10 Gn for 11 ms) Shocks contactor closed (15 Gn for 11 ms)
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
10.3 cm
Package 1 Width
8.1 cm
Package 1 Length
5.4 cm
Package 1 Weight
501.0 g
Warranty
18 months
Datasheet
Technical Data