LADS2

TIME ON DELAY BLOCK

Trade Price

£98.21

Per

1

Unit

EA

Pack Quantity

1

LADS2

Information

TeSys D time delay auxiliary contact block, for contactors LC1D, LC1F and control relays CAD. It provides 1NO+1NC contacts rated up to 10A 690V AC, Off-delay setting range 1-30s, connection by screw clamp terminals. A delay of 40ms is ensured between opening of NC contact and closing of NO contact. Clip-on front mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHs/Reach).

Technical Specifications

Range

TeSys TeSys Deca

Product name

TeSys Deca

Product or component type

Time delay auxiliary contact block

Range compatibility

TeSys Deca CAD TeSys Deca LC1D TeSys F LC1F TeSys F CR1F

Device application

Star delta starter

Mounting location

Front

Pole contact composition

1 NO + 1 NC

Contacts operation

Time delay

Timer type

On delay

Time delay range

1...30 s

[Ue] rated operational voltage

690 V AC 25...400 Hz

[Ie] rated operational current

6 A at 120 V AC-15 1.04 A at 690 V AC-15 0.55 A at 125 V DC-13 0.1 A at 600 V DC-13

[Ui] rated insulation voltage

690 V conforming to IEC 60947-5-1 600 V conforming to UL 60947-5-1 600 V conforming to CSA C22.2 No 60947-5-1

[Ith] conventional free air thermal current

10 A (at 60 °C)

standards

CSA C22.2 No 60947-5-1 GB/T 14048.5 EN/IEC 60947-5-1

product certifications

IECEE CB Scheme UL CSA CCC EAC UKCA

Irms rated making capacity

140 A at <= 690 V AC conforming to IEC 60947-5-1 250 A at <= 690 V DC conforming to IEC 60947-5-1

Permissible short-time rating

100 A 60 °C 1 s 120 A 60 °C 500 ms 140 A 60 °C 100 ms

Protection type

GG fuse 10 A

Mechanical durability

5 Mcycles

Minimum switching current

5 mA

Minimum switching voltage

17 V

Non-overlap time

1.5 ms on de-energisation no overlap between NC and NO contact 1.5 ms on energisation no overlap between NC and NO contact

Insulation resistance

> 10 MOhm

Connections - terminals

Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end Screw clamp terminals 1 cable(s) 1…2.5 mm²rigid Screw clamp terminals 2 cable(s) 1…2.5 mm²rigid Screw clamp terminals

Tightening torque

1.7 N.m - with screwdriver flat Ø 6 mm 1.7 N.m - with screwdriver Philips No 2 1.7 N.m - with screwdriver pozidriv No 2

height

48 mm

Width

44 mm

Depth

61 mm

Colour

Dark grey

Environmental characteristic

Normal environment

IP degree of protection

IP20 conforming to IEC 60529

Protective treatment

TH conforming to IEC 60068

Ambient air temperature for storage

-60…80 °C

Ambient air temperature for operation

-40…70 °C

Operating altitude

3000 m

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

5.2 cm

Package 1 Width

6.5 cm

Package 1 Length

4.8 cm

Package 1 Weight

82 g

Unit Type of Package 2

BB1

Number of Units in Package 2

10

Package 2 Height

5.2 cm

Package 2 Width

13 cm

Package 2 Length

24 cm

Package 2 Weight

836 g

Unit Type of Package 3

S03

Number of Units in Package 3

140

Package 3 Height

30 cm

Package 3 Width

30 cm

Package 3 Length

40 cm

Package 3 Weight

12.202 kg

Warranty

18 months

Document Links

Datasheet

Technical Data