Trade Price
£156.76
Per
1
Unit
EA
Pack Quantity
1
TeSys GV motor circuit breaker, 3 poles (3P), 18A/690V, for 3-phase motor applications 7.5kW@400V. It provides a thermal-magnetic protection with a thermal setting range 12-18A, magnetic tripping at 14xIn, high breaking capacity Icu 100kA@400V. Connection by Everlink BTR screw terminals. Start-stop control by rotary knob guaranteed for 50 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
Range
TeSys Deca
Product name
TeSys GV3 TeSys Deca
Product or component type
Motor circuit breaker
Device short name
GV3P
Device application
Motor protection
Trip unit technology
Thermal-magnetic
Poles description
3P
Network type
AC
Utilisation category
AC-3 conforming to IEC 60947-4-1
Network frequency
50/60 Hz conforming to IEC 60947-4-1
Fixing mode
35 mm symmetrical DIN rail: clipped Panel: screwed (with 3 x M4 screws)
Motor power kW
7.5 kW at 400/415 V AC 50/60 Hz 9 kW at 500 V AC 50/60 Hz 15 kW at 690 V AC 50/60 Hz
Breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
control type
Rotary handle
[In] rated current
18 A
Thermal protection adjustment range
12…18 A conforming to IEC 60947-4-1
Magnetic tripping current
252 A
[Ith] conventional free air thermal current
18 A conforming to IEC 60947-4-1
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
Phase failure sensitivity
Yes conforming to IEC 60947-4-1
Suitability for isolation
Yes conforming to IEC 60947-1
Power dissipation per pole
8 W
Mechanical durability
50000 cycles
Electrical durability
50000 cycles for AC-3 at 415 V In
Rated duty
Continuous conforming to IEC 60947-4-1
Tightening torque
5 N.m - on screw clamp terminal
Width
55 mm
height
132 mm
Depth
136 mm
Net weight
0.96 kg
Colour
Dark grey
Standards
EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1
product certifications
CCC UL CSA EAC ATEX LROS (Lloyds register of shipping) BV ABS DNV-GL UKCA
IK degree of protection
IK09 enclosure
IP degree of protection
IP20 conforming to IEC 60529
Climatic withstand
conforming to IACS E10
Ambient air temperature for storage
-40…80 °C
Fire resistance
960 °C conforming to IEC 60695-2-11
Ambient air temperature for operation
-20…60 °C
Mechanical robustness
Shocks: 15 Gn for 11 ms contactor open Shocks: 30 Gn for 11 ms contactor closed Vibrations: 4 Gn, 5...300 Hz
Operating altitude
3000 m
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
6.500 cm
Package 1 Width
16.000 cm
Package 1 Length
14.500 cm
Package 1 Weight
996.000 g
Unit Type of Package 2
P06
Number of Units in Package 2
60
Package 2 Height
75.000 cm
Package 2 Width
60.000 cm
Package 2 Length
80.000 cm
Package 2 Weight
72.760 kg
Warranty
18 months
Datasheet
Technical Data