GV2RT21

MOTOR CIRCUIT BREAKER 17-23A

Trade Price

£172.43

Per

1

Unit

EA

Pack Quantity

1

GV2RT21

Information

TeSys GV motor circuit breaker, 3 poles (3P), 23A/690V, for high starting current peak motor applications 9-11kW@400V. It provides a thermal-magnetic protection with a thermal setting range 17-23A, a magnetic tripping level at 17xIn, high breaking capacity Icu 15kA@400V. Connection by screw clamp terminals. Start-stop control by toggle guaranteed for 100 000 cycles AC-3. It can be used for protection of 3-phase transformer applications. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys Deca

Product name

TeSys GV2 TeSys Deca

Product or component type

Motor circuit breaker

Device short name

GV2RT

Device application

Motor protection

Trip unit technology

Thermal-magnetic

Poles description

3P

Network type

AC

Utilisation category

Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1

Network frequency

50/60 Hz conforming to IEC 60947-4-1

Fixing mode

35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)

Motor power kW

5.5 kW at 220/230 V AC 50/60 Hz motor protection high peak current 9 kW at 400/415 V AC 50/60 Hz motor protection high peak current 11 kW at 400/415 V AC 50/60 Hz motor protection high peak current 11 kW at 440 V AC 50/60 Hz motor protection high peak current 11 kW at 500 V AC 50/60 Hz motor protection high peak current 18.5 kW at 690 V AC 50/60 Hz motor protection high peak current

Breaking capacity

50 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2

Control type

Toggle

[In] rated current

23 A

Thermal protection adjustment range

17…23 A conforming to IEC 60947-4-1

Magnetic tripping current

400 A

[Ith] conventional free air thermal current

23 A conforming to IEC 60947-4-1

[Ue] rated operational voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

[Ui] rated insulation voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-2

Suitability for isolation

Yes conforming to IEC 60947-1 § 7-1-6

Power dissipation per pole

2.5 W

Mechanical durability

100000 cycles

Electrical durability

100000 cycles for AC-3 at 415 V In

Rated duty

Continuous conforming to IEC 60947-4-1

Tightening torque

1.7 N.m - on screw clamp terminal

Width

45 mm

height

89 mm

Depth

78.5 mm

standards

EN/IEC 60947-2 EN/IEC 60947-4-1

product certifications

CCC UL CSA EAC LROS (Lloyds register of shipping) BV UKCA

IK degree of protection

IK04

IP degree of protection

IP20 conforming to IEC 60529

Climatic withstand

conforming to IACS E10

Ambient air temperature for storage

-40…80 °C

Fire resistance

960 °C conforming to IEC 60695-2-11

Ambient air temperature for operation

-20…60 °C

Mechanical robustness

Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz

Operating altitude

2000 m

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

8.600 cm

Package 1 Width

9.300 cm

Package 1 Length

4.800 cm

Package 1 Weight

290.000 g

Unit Type of Package 2

S02

Number of Units in Package 2

24

Package 2 Height

15.000 cm

Package 2 Width

30.000 cm

Package 2 Length

40.000 cm

Package 2 Weight

7.169 kg

Unit Type of Package 3

P06

Number of Units in Package 3

288

Package 3 Height

75.000 cm

Package 3 Width

60.000 cm

Package 3 Length

80.000 cm

Package 3 Weight

97.480 kg

Warranty

18 months

Document Links

Datasheet

Technical Data