Trade Price
£143.50
Per
1
Unit
EA
Pack Quantity
1
TeSys GV motor circuit breaker, 3 poles (3P), 32A/690V, for 3-phase motor applications 15kW@400V. It provides a magnetic protection with a tripping level at 13xIn, high breaking capacity Icu 10kA@400V. Connection by screw clamp terminals. Start-stop control by toggle guaranteed for 100 000 cycles AC-3. To complete motor protection, use in association with a thermal overload relay LRD32 (to be ordered separately). Multi standards certified (IEC, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Range
TeSys Deca
Product name
TeSys GV2
Product or component type
Motor circuit breaker
Device short name
GV2LE
Device application
Motor protection
Trip unit technology
Magnetic
Poles description
3P
Network type
AC
Utilisation category
Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1
Network frequency
50/60 Hz conforming to IEC 60947-2
Fixing mode
35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)
Motor power kW
15 kW at 400/415 V AC 50/60 Hz 18.5 kW at 500 V AC 50/60 Hz 22 kW at 690 V AC 50/60 Hz
Breaking capacity
50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control type
Toggle
[In] rated current
32 A
Magnetic tripping current
416 A
[Ith] conventional free air thermal current
32 A conforming to IEC 60947-4-1
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
Suitability for isolation
Yes conforming to IEC 60947-1 § 7-1-6
Power dissipation per pole
1.8 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles for AC-3 at 415 V In
Rated duty
Continuous conforming to IEC 60947-4-1
Tightening torque
1.7 N.m - on screw clamp terminal
Width
45 mm
height
89 mm
Depth
78.5 mm
Net weight
0.33 kg
Colour
Dark grey
standards
EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1
product certifications
CCC UL EAC BV RINA UKCA
IK degree of protection
IK04
IP degree of protection
IP20 conforming to IEC 60529
Climatic withstand
conforming to IACS E10
Ambient air temperature for storage
-40…80 °C
Fire resistance
960 °C conforming to IEC 60695-2-11
Ambient air temperature for operation
-20…60 °C
Mechanical robustness
Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz
Operating altitude
2000 m
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.500 cm
Package 1 Width
9.300 cm
Package 1 Length
4.800 cm
Package 1 Weight
273.000 g
Unit Type of Package 2
S02
Number of Units in Package 2
24
Package 2 Height
15.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
6.863 kg
Unit Type of Package 3
P06
Number of Units in Package 3
384
Package 3 Height
75.000 cm
Package 3 Width
60.000 cm
Package 3 Length
80.000 cm
Package 3 Weight
125.604 kg
Warranty
18 months
Datasheet
Technical Data