CAD50M7

AUX CONT. 5NO 220V 50/60HZ

Trade Price

£48.51

Per

1

Unit

EA

Pack Quantity

1

CAD50M7

Information

TeSys D control relay, 5 contacts (5NO), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 220V 50/60Hz AC control circuit, connection by screw clamp terminals. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).

Technical Specifications

Range

TeSys TeSys Deca

Product name

TeSys CAD

Product or component type

Control relay

Device short name

CAD

contactor application

Control circuit

utilisation category

AC-15 AC-14 DC-13

Pole contact composition

5 NO

[Ue] rated operational voltage

<= 690 V AC 25...400 Hz

Control circuit type

AC at 50/60 Hz

[Uc] control circuit voltage

220 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

[Ith] conventional free air thermal current

10 A (at 60 °C)

Irms rated making capacity

140 A AC conforming to IEC 60947-5-1 250 A DC conforming to IEC 60947-5-1

[Icw] rated short-time withstand current

100 A - 1 s 120 A - 500 ms 140 A - 100 ms

Associated fuse rating

10 A gG conforming to IEC 60947-5-1

[Ui] rated insulation voltage

600 V UL certified 600 V CSA certified 690 V conforming to IEC 60947-5-1

mounting support

Plate Rail

Connections - terminals

Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end

Tightening torque

1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Control circuit voltage limits

0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz

Operating time

12...22 ms coil energisation and NO closing 4...12 ms coil de-energisation and NO opening

Mechanical durability

30 Mcycles

Maximum operating rate

180 cyc/mn

Inrush power in VA

70 VA 50 Hz (at 20 °C)

Hold-in power consumption in VA

8 VA 50 Hz (at 20 °C)

Minimum switching voltage

17 V

Minimum switching current

5 mA

Non-overlap time

1.5 ms on energisation between NC and NO contact 1.5 ms on de-energisation between NC and NO contact

Insulation resistance

> 10 MOhm

Mechanical robustness

Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6

height

77 mm

Width

45 mm

Depth

84 mm

Net weight

0.58 kg

Standards

EN/IEC 60947-5-1 GB/T 14048.5 UL 60947-5-1 CSA C22.2 No 60947-5-1 JIS C8201-5-1

product certifications

CB Scheme CCC UL CSA EAC CE UKCA

IP degree of protection

IP2X front face conforming to VDE 0106

Protective treatment

TH conforming to IEC 60068

Ambient air temperature for operation

-40…60 °C 60…70 °C with derating

Ambient air temperature for storage

-60…80 °C

Operating altitude

0...3000 m

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

5.500 cm

Package 1 Width

8.200 cm

Package 1 Length

9.500 cm

Package 1 Weight

352.000 g

Unit Type of Package 2

S02

Number of Units in Package 2

20

Package 2 Height

15.000 cm

Package 2 Width

30.000 cm

Package 2 Length

40.000 cm

Package 2 Weight

7.359 kg

Warranty

18 months

Document Links

Datasheet

Technical Data