Trade Price
£43.03
Per
1
Unit
EA
Pack Quantity
1
TeSys K control relay, 4 contacts (3NO + 1NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 24V DC control circuit with no inrush consumption, connection by solder pins for printed circuit boards. For high operating rates until 180 cycles/min and ambient temperature -25/+50°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium product (RoHS/REACh).
Range
TeSys
Product name
TeSys CAK
Product or component type
Control relay
Device short name
CA3K
contactor application
Control circuit
utilisation category
AC-15 DC-13
Pole contact composition
3 NO + 1 NC
[Ue] rated operational voltage
<= 690 V <= 400 Hz
Control circuit type
DC standard
[Uc] control circuit voltage
24 V DC
[Ith] conventional free air thermal current
10 A (at 50 °C)
Irms rated making capacity
110 A conforming to IEC 60947
Associated fuse rating
10 A gG conforming to IEC 60947 10 A gG conforming to VDE 0660
[Ui] rated insulation voltage
690 V conforming to IEC 60947 750 V conforming to VDE 0110 group C 690 V conforming to BS 5424 600 V conforming to CSA C22.2 No 14
mounting support
Plate Rail
Connections - terminals
Solder pins - busbar cross section: 1.5 x 0.9 mm
Control circuit voltage limits
Operational: 0.8...1.15 Uc (at <50 °C) Drop-out: 0.1...0.75 Uc (at <50 °C)
Operating time
10 ms coil de-energisation and NO opening 30...40 ms coil energisation and NO closing 15 ms coil de-energisation and NC closing 25...35 ms coil energisation and NC opening
Mechanical durability
20 Mcycles
Maximum operating rate
10000 cyc/h
Immunity to microbreaks
2 ms
Inrush power in W
3 W (at 20 °C)
Hold-in power consumption in W
3 W at 20 °C
Heat dissipation
3 W
Minimum switching voltage
17 V
Minimum switching current
5 mA
Non overlap distance
0.5 mm
Insulation resistance
> 10 MOhm
height
58 mm
Width
45 mm
Depth
57 mm
Net weight
0.255 kg
Standards
EN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1
product certifications
CB Scheme CCC UL CSA EAC CE UKCA
IP degree of protection
IP2X
Protective treatment
TC conforming to IEC 60068
Ambient air temperature for operation
-25…50 °C
Ambient air temperature for storage
-50…80 °C
Operating altitude
2000 m without derating
Flame retardance
V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
Mechanical robustness
Vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
6.5 cm
Package 1 Width
6.0 cm
Package 1 Length
4.8 cm
Package 1 Weight
252.0 g
Warranty
18 months
Datasheet
Technical Data