This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It features 3 built-in RJ45 communication ports as standard, 1 Ethernet port, 2 serial ports. It works at a rated supply voltage from 380V to 440V AC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 132kW for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 110kW for applications requiring significant overload (up to 150%). It weighs 310kg and its dimensions are, 400mm wide, 2350mm high, 669mm deep. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. Accessories (fan kit, graphic display terminal) and options (I/O expansion modules, communication modules, EMC input filters) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on the floor. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.
Range of product
Altivar Process ATV600
Product or component type
Variable speed drive
Product specific application
Process and utilities
Device short name
ATV650
Variant
With disconnect switch
Product destination
Asynchronous motors Synchronous motors
EMC filter
Integrated with 150 m conforming to EN/IEC 61800-3 category C3
IP degree of protection
IP54 conforming to IEC 60529 IP54 conforming to IEC 61800-5-1
[Us] rated supply voltage
380...440 V - 15...10 %
Type of cooling
Forced convection
Supply frequency
50...60 Hz - 5...5 %
Motor power kW
132 kW (normal duty) 110 kW (heavy duty)
Line current
210 A at 400 V (heavy duty) 179 A at 380 V (normal duty) 244 A at 380 V (heavy duty) 207 A at 400 V (normal duty)
Prospective line Isc
50 kA
Apparent power
160 kVA at 440 V (normal duty) 136 kVA at 440 V (heavy duty)
Continuous output current
250 A at 2.5 kHz for normal duty 211 A at 2.5 kHz for heavy duty
Asynchronous motor control profile
Variable torque standard Constant torque standard Constant torque standard
Synchronous motor control profile
Synchronous reluctance motor Permanent magnet motor
Speed drive output frequency
0.1…500 Hz
Nominal switching frequency
2.5 kHz
Switching frequency
2...8 kHz adjustable 2.5...8 kHz with derating factor
Safety function
STO (safe torque off) SIL 3
Discrete input logic
Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1) Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)
Communication port protocol
Modbus serial Ethernet Ethernet
Option card
Slot A: communication module, PROFINET Slot A: communication module, DeviceNet Slot A: communication module, Modbus TCP/EtherNet/IP Slot A: communication module, CANopen daisy chain RJ45 Slot A: communication module, CANopen SUB-D 9 Slot A: communication module, CANopen screw terminals Slot A/slot B: digital and analog I/O extension module Slot A/slot B: output relay extension module Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link Communication module, BACnet MS/TP Communication module, Ethernet Powerlink Slot A: communication module, Profibus DP V1
Mounting mode
Floor-standing
Maximum transient current
275 A during 60 s (normal duty) 317 A during 60 s (heavy duty)
Network number of phases
3 phases
Discrete output number
0
Discrete output type
Relay outputs R1A, R1B, R1C 250 V AC 3000 mA Relay outputs R1A, R1B, R1C 30 V DC 3000 mA Relay outputs R2A, R2C 250 V AC 5000 mA Relay outputs R2A, R2C 30 V DC 5000 mA Relay outputs R3A, R3C 250 V AC 5000 mA Relay outputs R3A, R3C 30 V DC 5000 mA
Output voltage
<= power supply voltage
Permissible temporary current boost
1.5 x In during 60 s (heavy duty) 1.1 x In during 60 s (normal duty)
Motor slip compensation
Not available in permanent magnet motor law Can be suppressed Automatic whatever the load Can be suppressed
Acceleration and deceleration ramps
Linear adjustable separately from 0.01...9999 s
Physical interface
Ethernet 2-wire RS 485
Braking to standstill
By DC injection
Protection type
Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive Thermal protection: motor
Transmission rate
10, 100 Mbits 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Frequency resolution
Analog input: 0.012/50 Hz Display unit: 0.1 Hz
Transmission frame
RTU
Electrical connection
Line side: M12 bar - 1 cables 3 x 150 mm² minimum per phase (normal duty) Line side: M12 bar - 2 cables 3 x 70 mm² minimum per phase (normal duty) Line side: M12 bar - 1 cables 3 x 185 mm² maximum per phase (normal duty) Line side: M12 bar - 2 cables 3 x 120 mm² maximum per phase (normal duty) Motor: M12 bar - 1 cables 3 x 120 mm² minimum per phase (normal duty) Motor: M12 bar - 2 cables 3 x 50 mm² minimum per phase (normal duty) Motor: M12 bar - 2 cables 3 x 185 mm² maximum per phase (normal duty) Line side: M12 bar - 1 cables 3 x 150 mm² minimum per phase (heavy duty) Line side: M12 bar - 2 cables 3 x 70 mm² minimum per phase (heavy duty) Line side: M12 bar - 1 cables 3 x 185 mm² maximum per phase (heavy duty) Line side: M12 bar - 2 cables 3 x 120 mm² maximum per phase (heavy duty) Motor: M12 bar - 1 cables 3 x 95 mm² minimum per phase (heavy duty) Motor: M12 bar - 2 cables 3 x 185 mm² maximum per phase (heavy duty) Control: removable screw terminals 0.5...1.5 mm²
Connector type
RJ45 (on the remote graphic terminal) for Modbus serial RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
Data format
8 bits, configurable odd, even or no parity
Type of polarization
No impedance
Exchange mode
Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Number of addresses
1…247 for Modbus serial
Method of access
Slave Modbus TCP
Supply
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection
Local signalling
3 LEDs (dual colour) for embedded communication status 4 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage 3 LEDs for local diagnostic
Width
400 mm
height
2350 mm
Depth
669 mm
Net weight
310 kg
analogue input number
3
Analogue input type
AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
Discrete input number
8
Discrete input type
DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
Input compatibility
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68 STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2 DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
analogue output number
2
Analogue output type
Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits Software-configurable current DQ-, DQ+: 30 V DC Software-configurable current DQ-, DQ+: 100 mA
Sampling duration
5 ms +/- 1 ms (DI5, DI6) - discrete input 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input 10 ms +/- 1 ms (AO1) - analog output 2 ms +/- 0.5 ms (DI1...DI4) - discrete input
Accuracy
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
Linearity error
AO1, AO2: +/- 0.2 % for analog output AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
Relay output number
3
Relay output type
Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
Refresh time
Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Minimum switching current
Relay output R1, R2, R3: 5 mA at 24 V DC
Maximum switching current
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
Isolation
Between power and control terminals
Maximum output frequency
500 kHz
Maximum input current
244.0 A
Variable speed drive application selection
Food and beverage processing other application Mining mineral and metal fan Mining mineral and metal pump Oil and gas fan Water and waste water other application Building - HVAC screw compressor Food and beverage processing pump Food and beverage processing fan Food and beverage processing atomization Oil and gas electro submersible pump (ESP) Oil and gas water injection pump Oil and gas jet fuel pump Oil and gas compressor for refinery Water and waste water centrifuge pump Water and waste water positive displacement pump Water and waste water electro submersible pump (ESP) Water and waste water screw pump Water and waste water lobe compressor Water and waste water screw compressor Water and waste water compressor centrifugal Water and waste water fan Water and waste water conveyor Water and waste water mixer Building - HVAC compressor centrifugal
Motor power range AC-3
110…220 kW at 480…500 V 3 phases 110…220 kW at 380…440 V 3 phases
Quantity per set
1
Enclosure mounting
Floor-standing
Insulation resistance
> 1 MOhm 500 V DC for 1 minute to earth
Noise level
69 dB
Power dissipation in W
2010 W, switching frequency 2.5 kHz (heavy duty) 3150 W, switching frequency 2.5 kHz (normal duty)
Volume of cooling air
720 m3/h
Operating position
Vertical +/- 10 degree
Maximum THDI
<48 % full load conforming to IEC 61000-3-12
Electromagnetic compatibility
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Pollution degree
3
Vibration resistance
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Relative humidity
5…95 % without condensation conforming to IEC 60068-2-3
Ambient air temperature for operation
40…50 °C (with derating factor) -15…40 °C (without derating)
Ambient air temperature for storage
-40…70 °C
Operating altitude
1000...4800 m with current derating 1 % per 100 m <= 1000 m without derating
product certifications
ATEX EAC C-Tick
Marking
CE
standards
EN/IEC 60204-1 EN/IEC 61800-2 EN/IEC 61800-3 EN/IEC 61800-5-1
Overvoltage category
III
Regulation loop
Adjustable PID regulator
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
214.5 cm
Package 1 Width
120.0 cm
Package 1 Length
110.5 cm
Package 1 Weight
383.0 kg
Warranty
18 months