Trade Price
£133.85
Per
1
Unit
EA
Pack Quantity
1
TeSys GV motor circuit breaker, 3 poles (3P), 10A/690V, for high starting current peak motor applications 3-4kW@400V. It provides a thermal-magnetic protection with a thermal setting range 6-10A, a magnetic tripping level at 20xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by toggle guaranteed for 100 000 cycles AC-3. It can be used for protection of 3-phase transformer applications. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Range
TeSys Deca
Product name
TeSys GV2 TeSys Deca
Product or component type
Motor circuit breaker
Device short name
GV2RT
Device application
Motor protection Motor
Trip unit technology
Thermal-magnetic
Poles description
3P
Network type
AC
Utilisation category
Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1
Network frequency
50/60 Hz conforming to IEC 60947-4-1
Fixing mode
35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)
Motor power kW
1.5 kW at 220/230 V AC 50/60 Hz motor protection high peak current 2.2 kW at 220/230 V AC 50/60 Hz motor protection high peak current 3 kW at 400/415 V AC 50/60 Hz motor protection high peak current 4 kW at 400/415 V AC 50/60 Hz motor protection high peak current 4 kW at 440 V AC 50/60 Hz motor protection high peak current 4 kW at 500 V AC 50/60 Hz motor protection high peak current 5.5 kW at 500 V AC 50/60 Hz motor protection high peak current 5.5 kW at 690 V AC 50/60 Hz motor protection high peak current 7.5 kW at 690 V AC 50/60 Hz motor protection high peak current 2.5 kW at 230/240 V AC 50/60 Hz transformer protection 4 kW at 400/415 V AC 50/60 Hz transformer protection 5 kW at 400/415 V AC 50/60 Hz transformer protection 5 kW at 440 V AC 50/60 Hz transformer protection 5 kW at 500 V AC 50/60 Hz transformer protection 6.3 kW at 500 V AC 50/60 Hz transformer protection
Breaking capacity
100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control type
Toggle
[In] rated current
10 A
Thermal protection adjustment range
6…10 A conforming to IEC 60947-4-1
Magnetic tripping current
200 A
[Ith] conventional free air thermal current
10 A conforming to IEC 60947-4-1
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
Suitability for isolation
Yes conforming to IEC 60947-1 § 7-1-6
Power dissipation per pole
2.5 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles for AC-3 at 415 V In
Rated duty
Continuous conforming to IEC 60947-4-1
Tightening torque
1.7 N.m - on screw clamp terminal
Width
45 mm
height
89 mm
Depth
78.5 mm
standards
EN/IEC 60947-2 EN/IEC 60947-4-1
product certifications
CCC UL CSA EAC LROS (Lloyds register of shipping) BV UKCA
IK degree of protection
IK04
IP degree of protection
IP20 conforming to IEC 60529
Climatic withstand
conforming to IACS E10
Ambient air temperature for storage
-40…80 °C
Fire resistance
960 °C conforming to IEC 60695-2-11
Ambient air temperature for operation
-20…60 °C
Mechanical robustness
Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz
Operating altitude
2000 m
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
4.7 cm
Package 1 Width
9.5 cm
Package 1 Length
8.5 cm
Package 1 Weight
278 g
Unit Type of Package 2
S02
Number of Units in Package 2
24
Package 2 Height
15 cm
Package 2 Width
30 cm
Package 2 Length
40 cm
Package 2 Weight
6.953 kg
Unit Type of Package 3
P06
Number of Units in Package 3
288
Package 3 Height
75 cm
Package 3 Width
60 cm
Package 3 Length
80 cm
Package 3 Weight
92.872 kg
Warranty
18 months
Datasheet
Technical Data