LP1D40008BD

Cont.-2NO 2NC 60A AC1 poles

Trade Price

£352.59

Per

1

Unit

EA

Pack Quantity

1

LP1D40008BD

Information

TeSys Deca contactor, 4 poles (2NO+2NC), for non-inductive load applications up to 60A/690V AC-1. It provides a 24V DC coil, power connection by screw terminals, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (85mm width), DIN-rail mounting or screw fixing. Without build-in auxiliary contacts, front mounting auxiliary contact blocks can be added (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys

Range of product

TeSys Deca

Product or component type

Contactor

Device short name

LP1D

contactor application

Resistive load

utilisation category

AC-1

Poles description

4P

[Ue] rated operational voltage

Power circuit: <= 1000 V AC 25...400 Hz

[Ie] rated operational current

60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

[Uc] control circuit voltage

24 V DC

Compatibility code

LP1D

Pole contact composition

2 NO + 2 NC

Contact compatibility

M3

Protective cover

Without

[Ith] conventional free air thermal current

60 A (at 60 °C) for power circuit

Irms rated making capacity

800 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity

800 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current

72 A 40 °C - 10 min for power circuit 165 A 40 °C - 1 min for power circuit 320 A 40 °C - 10 s for power circuit 720 A 40 °C - 1 s for power circuit

Associated fuse rating

80 A gG at <= 690 V coordination type 1 for power circuit 80 A gG at <= 690 V coordination type 2 for power circuit

Average impedance

1.5 mOhm - Ith 60 A 50 Hz for power circuit

Power dissipation per pole

5.4 W AC-1

[Ui] rated insulation voltage

Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified

Overvoltage category

III

Pollution degree

3

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability

10 Mcycles

Electrical durability

1.4 Mcycles 60 A AC-1 at Ue <= 440 V

Control circuit type

DC DC standard

Coil technology

Built-in bidirectional peak limiting diode suppressor

Control circuit voltage limits

0.1...0.3 Uc (-40…70 °C):drop-out DC 0.85...1.1 Uc (-40…55 °C):operational DC 1...1.1 Uc (55…70 °C):operational DC

Inrush power in W

22 W (at 20 °C)

Hold-in power consumption in W

22 W at 20 °C

Operating time

4...19 ms opening 12...26 ms closing

Time constant

75 ms

Maximum operating rate

3600 cyc/h 60 °C

Connections - terminals

Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: solid Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid

Tightening torque

Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

mounting support

Plate Rail

Standards

CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508

product certifications

UL CSA CCC EAC UKCA CB DNV-GL RINA BV LROS (Lloyds register of shipping)

IP degree of protection

IP20 front face conforming to IEC 60529

Permissible ambient air temperature around the device

-40…60 °C 60…70 °C with derating

Operating altitude

0...3000 m

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V1 conforming to UL 94

Mechanical robustness

Shocks contactor open (8 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz)

height

127 mm

Width

85 mm

Depth

182 mm

Net weight

2.21 kg

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

11.0 cm

Package 1 Width

16.2 cm

Package 1 Length

21.8 cm

Package 1 Weight

2.265 kg

Unit Type of Package 2

S02

Number of Units in Package 2

2

Package 2 Height

15 cm

Package 2 Width

30 cm

Package 2 Length

40 cm

Package 2 Weight

4.828 kg

Warranty

18 months

Document Links

Datasheet

Technical Data