Trade Price
£48.88
Per
1
Unit
EA
Pack Quantity
12
Range
TeSys
Product name
TeSys GF
Product or component type
Impulse relay
Device short name
GF16
utilisation category
AC-1
Poles description
2P
Pole contact composition
1 NO + 1 NC
[Ie] rated operational current
16 A AC-1
[Ue] rated operational voltage
250 V AC 50/60 Hz
Permissible short-time rating
320 A 40 °C 1 s 48 A 40 °C 30 s 96 A 40 °C 10 s
Operating position
+/- 90° to vertical plane
Control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
24 V AC 50/60 Hz
Mounting mode
Clip-on
mounting support
35 mm symmetrical DIN rail
[Ith] conventional free air thermal current
16 A (at 50 °C)
Average impedance
4 mOhm at 50 Hz - Ith 16 A
[Ui] rated insulation voltage
400 V conforming to IEC 60947-5-1 400 V conforming to VDE 0110
[Uimp] rated impulse withstand voltage
4 kV in enclosure
Connections - terminals
Control circuit: screw clamp terminals 1 cable(s) 1.5 mm² solid without cable end Control circuit: screw clamp terminals 1 cable(s) 2.5 mm² flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 2.5 mm² flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1.5 mm² flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1.5 mm² solid without cable end Control circuit: screw clamp terminals 2 cable(s) 2.5 mm² flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 0.5…6 mm² flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 0.5…6 mm² flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 0.5…6 mm² solid without cable end Power circuit: screw clamp terminals 2 cable(s) 0.5…4 mm² flexible with cable end Power circuit: screw clamp terminals 2 cable(s) 0.5…4 mm² flexible without cable end Power circuit: screw clamp terminals 2 cable(s) 0.5…4 mm² solid without cable end
Tightening torque
Control circuit: 0.8 N.m - on screw clamp terminals Power circuit: 0.8 N.m - on screw clamp terminals
Operating time
70 ms closing 70 ms opening
Maximum operating rate
900 cyc/h
Control circuit voltage limits
0.85...1.1 Uc 50 °C 50/60 Hz
impulse duration
>= 70 ms
Average consumption
19 VA AC 50 Hz at at Uc at 20 ºC
Power dissipation per pole
1 W
Mechanical durability
1 Mcycles
Electrical durability
100000 cycles AC-22 200000 cycles AC-21
9 mm pitches
2
height
81 mm
Width
18 mm
Depth
64 mm
Net weight
0.11 kg
Quantity per set
Set of 12
standards
IEC 60669-1 NF C 61-112 IEC 60669-2
IP degree of protection
IP40 conforming to VDE 0106 (in enclosure) IP20 conforming to VDE 0106
Protective treatment
TC
Ambient air temperature for operation
-20…50 °C
Ambient air temperature for storage
-40…80 °C
Operating altitude
<= 2000 m without derating
Mechanical robustness
Vibrations contactor open: 4 Gn, 5...300 Hz Vibrations contactor closed: 4 Gn, 5...300 Hz
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.0 cm
Package 1 Width
9.4 cm
Package 1 Length
23.0 cm
Package 1 Weight
120.0 g
Unit Type of Package 2
BB1
Number of Units in Package 2
12
Package 2 Height
8.0 cm
Package 2 Width
9.4 cm
Package 2 Length
23.0 cm
Package 2 Weight
1.44 kg
Unit Type of Package 3
S02
Number of Units in Package 3
48
Package 3 Height
15.0 cm
Package 3 Width
30.0 cm
Package 3 Length
40.0 cm
Package 3 Weight
6.143 kg
Warranty
18 months
Datasheet
Technical Data