Trade Price
£741.84
Per
1
Unit
EA
Pack Quantity
1
TeSys Deca contactor, 4-pole (4NO), for non-inductive load applications up to 200A/1000V AC-1. It provides a 24V DC coil with transient suppressor module, power connection by screw connectors 2 inputs, control connection by screw clamp terminals. For operating rates until 1200 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (150mm width), mounting on 2 DIN-rails or screw fixing. Without build-in auxiliary contacts, side and front mounting auxiliary contact blocks available (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Range
TeSys
Range of product
TeSys Deca
Product or component type
Contactor
Device short name
LC1D
contactor application
Resistive load
utilisation category
AC-1 AC-3 AC-3e AC-4
Poles description
4P
[Ue] rated operational voltage
Power circuit: <= 1000 V AC 25...400 Hz Power circuit: <= 460 V DC
[Ie] rated operational current
200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
24 V DC
Compatibility code
LC1D
Pole contact composition
4 NO
Contact compatibility
M8
Protective cover
With
[Ith] conventional free air thermal current
200 A (at 60 °C) for power circuit
Irms rated making capacity
1260 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
250 A 40 °C - 10 min for power circuit 550 A 40 °C - 1 min for power circuit 950 A 40 °C - 10 s for power circuit 1100 A 40 °C - 1 s for power circuit
Associated fuse rating
250 A gG at <= 690 V coordination type 1 for power circuit 200 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
0.6 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole
24 W AC-1
[Ui] rated insulation voltage
Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Power circuit: 1000 V conforming to IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability
8 Mcycles
Electrical durability
0.8 Mcycles 200 A AC-1 at Ue <= 440 V
Control circuit type
DC standard
Coil technology
With integral suppression device
Control circuit voltage limits
0.75...1.2 Uc (-40…55 °C):operational DC 0.15...0.4 Uc (-40…70 °C):drop-out DC 1...1.2 Uc (55…70 °C):operational DC
Inrush power in W
270…365 W (at 20 °C)
Hold-in power consumption in W
2.4…5.1 W at 20 °C
Operating time
20...35 ms closing 40...75 ms opening
Time constant
25 ms
Maximum operating rate
1200 cyc/h 60 °C
Connections - terminals
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable end Power circuit: connector 1 10…120 mm² - cable stiffness: flexible without cable end Power circuit: connector 2 10…50 mm² - cable stiffness: flexible without cable end Power circuit: connector 1 10…120 mm² - cable stiffness: flexible with cable end Power circuit: connector 2 10…50 mm² - cable stiffness: flexible with cable end Power circuit: connector 1 10…120 mm² - cable stiffness: solid without cable end Power circuit: connector 2 10…50 mm² - cable stiffness: solid without cable end
Tightening torque
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 12 N.m - on connector hexagonal screw head 4 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
mounting support
Rail Plate
Standards
CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
product certifications
RINA GOST GL CCC DNV BV CSA UL LROS (Lloyds register of shipping) UKCA
IP degree of protection
IP20 front face conforming to IEC 60529
Protective treatment
TH conforming to IEC 60068-2-30
Climatic withstand
conforming to IACS E10 exposure to damp heat conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device
-40…60 °C 60…70 °C with derating
Operating altitude
0...3000 m
Fire resistance
850 °C conforming to IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations contactor open (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz) Shocks contactor closed (15 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)
height
158 mm
Width
150 mm
Depth
132 mm
Net weight
2.86 kg
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
16.8 cm
Package 1 Width
21.2 cm
Package 1 Length
18.5 cm
Package 1 Weight
2.75 kg
Warranty
18 months
Datasheet
Technical Data