LT4760BS

ELEC RLY 5A 60A 24V ACDC MAN

Trade Price

£102.94

Per

1

Unit

EA

Pack Quantity

1

LT4760BS

Information

TeSys LR47 electronic overcurrent relay, 60A/690V, with manual reset, to be supplied with 24V AC/DC, for protection of motors with a rated current 5-50A. It provides 3 dials to adjust the protection, LOAD (5-60A) for the overcurrent level, O-TIME (0.3-10sec) for the acceptable duration of the overcurrent, D-TIME (0.5-30sec) for the starting duration. In addition, the device trips when there is a missing phase during more than O-TIME. The device has a reset button, a test/stop button, 2 LED indicators (Run/Trip), 2 auxiliary contacts 1NO+1NC for fault signalling. Settings can be locked by sealing the transparent cover. DIN rail mounting, without power terminals (currents monitored by 2 current transformers crossed by the motor cables). Multi standards certified (IEC, UL, CSA, CCC, EAC), it conforms to RoHS/REACh regulation.

Technical Specifications

Range

TeSys

Product name

TeSys LT

Product or component type

Electronic over current relay

Device short name

LT47

Device application

Protection

Relay application

Overload Imax > Isetting Sensitivity to phase failure Locked rotor, mechanical jamming I > 3 x Isetting

[Us] rated supply voltage

24 V AC 24 V DC

Thermal protection adjustment range

5…60 A

[Ui] rated insulation voltage

Power circuit: 600 V AC conforming to CSA Power circuit: 600 V AC conforming to UL Power circuit: 690 V AC conforming to IEC 60947-4-1

Network frequency

50...60 Hz

Mounting support

Rail

Tripping threshold

5...50 A

Electromagnetic compatibility

Resistance to electrostatic discharge: 8 kV in open air conforming to IEC 61000-4-2 Resistance to electrostatic discharge: 6 kV in direct mode conforming to IEC 61000-4-2 Conducted emission: class A conforming to EN 55011 Immunity to electromagnetic interference: 10 V/m conforming to IEC 61000-4-3 Immunity to fast transients: 2 kV conforming to IEC 61000-4-4 Surge withstand: 6 kV conforming to IEC 61000-4-5 Conducted HF disturbances: 10 V conforming to IEC 61000-4-6

Auxiliary contact composition

1 NO + 1 NC

[Ith] conventional free air thermal current

3 A for signalling circuit

Associated fuse rating

3 A gG for signalling circuit 3 A BS for signalling circuit

[Uimp] rated impulse withstand voltage

6 kV

Time range

0.5..30 s - control type D-time 0.3...10 s - control type O-time

Local signalling

1 LED (green) 1 LED (red)

Control type

push-button: reset electrical: reset

Connections - terminals

Signalling circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end Signalling circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end Signalling circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Signalling circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end

Tightening torque

Signalling circuit: 1.7 N.m M3.5

height

70.3 mm

Width

71 mm

Depth

77.2 mm

Net weight

0.192 kg

standards

IEC 60947 IEC 60255-6

product certifications

CSA UL

Protective treatment

TH conforming to IEC 60068

IP degree of protection

IP20 conforming to IEC 60529 IP20 conforming to VDE 0106

Ambient air temperature for operation

-25…60 °C without derating conforming to IEC 60947-4-1

Ambient air temperature for storage

-30…80 °C

Operating altitude

2000 m

Mechanical robustness

Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7 Vibrations: 4 gn conforming to IEC 60068-2-6

Dielectric strength

2 kV at 50 Hz conforming to IEC 60255-5

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

7 cm

Package 1 Width

8 cm

Package 1 Length

8.7 cm

Package 1 Weight

191 g

Unit Type of Package 2

S02

Number of Units in Package 2

16

Package 2 Height

15 cm

Package 2 Width

30 cm

Package 2 Length

40 cm

Package 2 Weight

3.525 kg

Warranty

18 months

Document Links

Datasheet

Technical Data