K2D002W

K2CAM REV 2P F 0

Trade Price

£14.86

Per

1

Unit

EA

Pack Quantity

1

K2D002W

Technical Specifications

Range of produc

Harmony K

Product or component type

Cam switch body

component name

K2

[Ith] conventional free air thermal current

20 A

Sub-assembly composition

Contact blocks + fixing plate

Cam switch function

Reversing switch

Off position

With Off position

Poles description

2P

Switching positions

Left: 0° - 315° Right: 0° - 45°

Product mounting

Front mounting

Fixing mode

Ø 22 mm hole

bezel material

Plastic

Switching angle

45 °

[Ui] rated insulation voltage

690 V (pollution degree 3) conforming to IEC 60947-1

[Ithe] conventional enclosed thermal current

16 A

Rated operational power in W

1300 W AC-3, 230 V 1 phase conforming to IEC 947-3 14000 W AC-21, 400 V 3 phases conforming to IEC 947-3 17000 W AC-21, 500 - 660 V 3 phases conforming to IEC 947-3 2200 W AC-3, 230 V 3 phases conforming to IEC 947-3 2200 W AC-3, 400 V 1 phase conforming to IEC 947-3 4000 W AC-23A, 230 V 3 phases conforming to IEC 947-3 4000 W AC-3, 400 V 3 phases conforming to IEC 947-3 4000 W AC-3, 500 V 3 phases conforming to IEC 947-3 4000 W AC-3, 690 V 3 phases conforming to IEC 947-3 5500 W AC-23A, 400 V 3 phases conforming to IEC 947-3 5500 W AC-23A, 500 V 3 phases conforming to IEC 947-3 5500 W AC-23A, 690 V 3 phases conforming to IEC 947-3 8000 W AC-21, 230 V 3 phases conforming to IEC 947-3

[Ie] rated operational current AC

2 A at 500 V AC-15 conforming to IEC 947-5-1 3 A at 400 V AC-15 conforming to IEC 947-5-1 4 A at 230 V AC-15 conforming to IEC 947-5-1 8 A at 400 V AC-3 3 phases conforming to IEC 947-3 10.8 A at 400 V AC-23A 3 phases conforming to IEC 947-3 14.6 A at 230 V AC-23A 3 phases conforming to IEC 947-3 4.7 A at 690 V AC-3 3 phases conforming to IEC 947-3 6.4 A at 690 V AC-23A 3 phases conforming to IEC 947-3 6.5 A at 500 V AC-3 3 phases conforming to IEC 947-3 8.3 A at 230 V AC-3 3 phases conforming to IEC 947-3 8.9 A at 500 V AC-23A 3 phases conforming to IEC 947-3

Electrical durability

200000 cycles AC-23 200000 cycles AC-3 600000 cycles AC-15 600000 cycles AC-21

Maximum operating rate

2.5 cyc/mn AC-21 2.5 cyc/mn AC-23 2.5 cyc/mn AC-3 8.333 cyc/mn AC-15

Short-circuit current

10000 A

Short-circuit protection

20 A cartridge fuse, type gG

[Uimp] rated impulse withstand voltage

4 kV in isolating function 6 kV conforming to IEC 947-1

contact operation

Slow-break

Positive opening

With

Electrical connection

Captive screw clamp terminals flexible, clamping capacity: 2 x 1.5 mm² Captive screw clamp terminals solid, clamping capacity: 1 x 2.5 mm²

Mechanical durability

1000000 cycles

Net weight

0.11 kg

Standards

CENELEC EN 50013 EN 60947-3 for power circuit EN 60947-5-1 for control circuit IEC 60947-3 for power circuit IEC 60947-5-1 for control circuit

Product certifications

CSA 240 V 1 hp 1 phase CSA 240 V 3 hp 3 phases 2 pole(s) UL 240 V 1 hp 3 phases UL 240 V 0.33 hp 1 phase 2 pole(s)

Protective treatment

TC

ambient air temperature for operation

-25…55 °C

Ambient air temperature for storage

-40…70 °C

Shock resistance

30 gn conforming to IEC 68-2-27

Vibration resistance

5 gn conforming to IEC 68-2-6 (f = 10…150 Hz)

Electrical shock protection class

Class II conforming to IEC 536 Class II conforming to NF C 20-030

Warranty

18 months

Document Links