This Harmony RM35-JA relay allows monitoring of current control in single phase networks. This modular multi function single phase current control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC.

Technical Specifications

Range of produc

Harmony Control Relays

Relay type

Current control relay

Product or component type

Current control relay

Relay name

RM35JA

Relay monitored parameters

Overcurrent or undercurrent in window mode Overcurrent or undercurrent detection

time delay

Adjustable 1...20 s, 0 + 10 % on energisation Ti Adjustable 0.3...30 s, 0 + 10 % on crossing the threshold Tt

Switching capacity in VA

1250 VA

Minimum switching current

10 mA at 5 V DC

Maximum switching current

5 A AC

Maximum power consumption in VA

3.5 VA AC

Measurement range

10...100 mA E2-M terminals 2...20 mA E1-M terminals 2...500 mA current 50...500 mA E3-M terminals

Utilisation category

AC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 DC-14 conforming to IEC 60947-5-1

Contacts type and composition

2 C/O

Reset time

1500 ms time delay

Maximum switching voltage

250 V AC

Supply voltage limits

20.4…264 V AC/DC

operating voltage tolerance

- 15 % + 10 % Un

Maximum power consumption in W

0.6 W DC

control circuit frequency

40...70 Hz +/- 10 %

Resistance across terminals

1 Ohm at E2-M terminals 5 Ohm at E1-M terminals 0.2 Ohm at E3-M terminals

Output contacts

2 C/O

Nominal output current

5 A

Maximum measuring cycle

30 ms measurement cycle as true rms value

Hysteresis

5…50 % of threshold setting

delay at power up

0.3 s

Measurement accuracy

+/- 10 % of the full scale value

Repeat accuracy

+/- 0.5 % for input and measurement circuit +/- 2 % for time delay

Measurement error

0.05 %/°C with temperature variation 1 by volt over the whole range with voltage variation

Polarity

No DC

Threshold setting

10...100 %

Marking

CE : EMC 89/336/EEC CE : 73/23/EEC

Overvoltage category

III conforming to IEC 60664-1

Insulation resistance

> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5 > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1 > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5 > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1 > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5 > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1

[Ui] rated insulation voltage

250 V conforming to IEC 60664-1

Operating position

Any position without derating

Connections - terminals

Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end

Tightening torque

0.6…1 N.m conforming to IEC 60947-1

Housing material

Self-extinguishing plastic

Local signalling

LED (green) for power ON LED (yellow) for relay ON

Mounting support

35 mm symmetrical DIN rail conforming to IEC 60715

Electrical durability

100000 cycles

Mechanical durability

30000000 cycles

Operating rate

<= 360 operations/hour full load

Safety reliability data

MTTFd = 296.8 years B10d = 270000

Contacts material

Cadmium free

Width

35 mm

Net weight

0.13 kg

Immunity to microbreaks

50 ms

Electromagnetic compatibility

Emission standard for industrial environments conforming to IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 Immunity for industrial environments conforming to NF EN/IEC 61000-6-2

Standards

IEC 60255-6

product certifications

GL CSA GOST UL C-Tick

Ambient air temperature for storage

-40…70 °C

Ambient air temperature for operation

-20…50 °C

Relative humidity

95 % at 55 °C conforming to IEC 60068-2-30

Vibration resistance

0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6 1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1

Shock resistance

15 gn for 11 ms conforming to IEC 60255-21-1

IP degree of protection

IP20 (terminals) conforming to IEC 60529 IP30 (casing) conforming to IEC 60529

Pollution degree

3 conforming to IEC 60664-1

Dielectric test voltage

2 kV, 1 min AC 50 Hz conforming to IEC 60255-5 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1

Non-dissipating shock wave

4 kV conforming to IEC 60255-5 4 kV conforming to IEC 60664-1 4 kV conforming to IEC 61000-4-5

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

4.500 cm

Package 1 Width

7.800 cm

Package 1 Length

9.500 cm

Package 1 Weight

138.000 g

Unit Type of Package 2

S03

Number of Units in Package 2

48

Package 2 Height

30.000 cm

Package 2 Width

30.000 cm

Package 2 Length

40.000 cm

Package 2 Weight

7.350 kg

Warranty

18 months

Document Links

Datasheet

Technical Data