This Harmony RM17-TG relay allows monitoring of power supply circuits in 3-phase networks. This modular multi function 3-phase supply control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slimmest form-factors with 17.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. The product monitors its own power supply, when the power supply is abnormal, the output relay de-energizes. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0
Range of product
Harmony Control Relays
Product or component type
3-phase control relay
Relay type
Control relay
Product specific application
For 3-phase supply
Relay name
RM17TG
Relay monitored parameters
Phase sequence Phase failure detection (2 or more phase cut)
time delay
Without
Switching capacity in VA
1250 VA
Measurement range
208...440 V voltage AC
Contacts type and composition
2 C/O
[Uc] control circuit voltage
208...440 V
Maximum switching voltage
250 V AC 250 V DC
Minimum switching current
10 mA at 5 V DC
Supply voltage limits
183…484 V AC
Control circuit voltage limits
- 12 % + 10 % Un
Power consumption in VA
0…22 VA at 400 V AC 50 Hz
Voltage detection threshold
< 100 V AC
control circuit frequency
50...60 Hz +/- 10 %
Output contacts
2 C/O
Nominal output current
5 A
Measurement voltage limits
183…484 V AC
delay at power up
650 ms
Voltage range
183...484 V
Response time
<= 130 ms (in the event of a fault)
Marking
CE
Overvoltage category
III conforming to IEC 60664-1
Insulation resistance
> 500 MOhm at 500 V DC conforming to IEC 60255-5 > 500 MOhm at 500 V DC conforming to IEC 60664-1
[Ui] rated insulation voltage
400 V conforming to IEC 60664-1
Supply frequency
50/60 Hz +/- 10 %
Operating position
Any position without derating
Connections - terminals
Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque
0.6…1 N.m conforming to IEC 60947-1
Housing material
Self-extinguishing plastic
Local signalling
LED (yellow) for relay ON
Mounting support
35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability
10000 cycles
Mechanical durability
30000000 cycles
Operating rate
<= 360 operations/hour full load
Utilisation category
AC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1
Safety reliability data
B10d = 850000 MTTFd = 924.6 years
Width
17.5 mm
Net weight
0.13 kg
Electromagnetic compatibility
Emission standard for industrial environments conforming to IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 Immunity for industrial environments conforming to IEC 61000-6-2
standards
IEC 60255-1
product certifications
GOST C-Tick UL CSA GL
Directives
73/23/EEC - low voltage directive 89/336/EEC - electromagnetic compatibility
Ambient air temperature for storage
-40…70 °C
Ambient air temperature for operation
-20…50 °C
Relative humidity
95 % at 55 °C conforming to IEC 60068-2-30
Vibration resistance
0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6 1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
Shock resistance
15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protection
IP20 (terminals) conforming to IEC 60529 IP30 (casing) conforming to IEC 60529
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
2 kV, 1 min AC 50 Hz
Non-dissipating shock wave
4 kV
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
2.700 cm
Package 1 Width
7.800 cm
Package 1 Length
9.700 cm
Package 1 Weight
98.000 g
Unit Type of Package 2
S02
Number of Units in Package 2
48
Package 2 Height
15.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
5.150 kg
Unit Type of Package 3
P06
Number of Units in Package 3
768
Package 3 Height
75.000 cm
Package 3 Width
60.000 cm
Package 3 Length
80.000 cm
Package 3 Weight
87.204 kg
Warranty
18 months
Datasheet
Technical Data