LUFDA01

1 NC FAULT DIF MODULE AUTORST

Trade Price

£105.31

Per

1

Unit

EA

Pack Quantity

1

LUFDA01

Information

TeSys U additional function module to be inserted in advanced power bases LUB120, LUB320, LUB380 for thermal overload tripping indication. It indicates the overload tripping and reset done by the power base control pad or done remotely. It provides 1NC instantaneous contact rated 24-250V AC/DC 5A max. It requires an external power supply 24-240V AC or DC. To be inserted in the cavity of a power base provided for the auxiliary modules. Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys

Device short name

LUF

Product or component type

Function module

Product compatibility

LUCB LUCC LUCD

Mounting mode

Plug-in

Mounting location

Front side

main function available

Thermal overload signalling and automatic or remote reset

Auxiliary contact composition

1 NC

Communication of faults

LED front panel

[Us] rated supply voltage

24...240 V DC

[Ith] conventional free air thermal current

2 A 70 °C

Short-circuit protection

2 A fuse gG conforming to IEC 60947-5-1

Connection pitch

5.08 mm

Tightening torque

0.5…0.6 N.m - with screwdriver 3.5 mm flat

Net weight

0.055 kg

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

3.300 cm

Package 1 Width

4.700 cm

Package 1 Length

10.500 cm

Package 1 Weight

74.000 g

Unit Type of Package 2

S01

Number of Units in Package 2

20

Package 2 Height

15.000 cm

Package 2 Width

15.000 cm

Package 2 Length

40.000 cm

Package 2 Weight

1.697 kg

Warranty

18 months

Document Links

Datasheet