LUALB1

130 KA LIMITER

Trade Price

£79.28

Per

1

Unit

EA

Pack Quantity

1

LUALB1

Information

TeSys U short circuit current limiter block to be connected in series and upstream of a TeSys U starter controller. It increases the starter controller ability to withstand the short circuit current from 50 kA to 130 kA under 400 V. It includes a limiter cartridge LUALF1. To be mounted directly on the upstream terminals of a power base, it must be connected to one power base only. Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys

Range of product

TeSys Ultra

Device short name

LUA

Product or component type

Limiter disconnector

Product compatibility

LUB LU2B

[Ith] conventional free air thermal current

32 A

Activation threshold

50 kA

Breaking capacity

70 kA at 690 V 130 kA at <= 440 V

[Ui] rated insulation voltage

690 V conforming to EN 60947-1 690 V conforming to IEC 60947-1

Mounting mode

Direct

Connections - terminals

Connector 1 x 1…10 mm² flexible without cable end Connector 1 x 1…6 mm² flexible with cable end Connector 2 x 1…6 mm² flexible with cable end Connector 2 x 1…6 mm² flexible without cable end Connector 1 x 1.5…10 mm² solid Connector 2 x 1.5…6 mm² solid

Tightening torque

1.9…2.5 N.m flat Ø 6 mm 1.9…2.5 N.m Philips No 2

Net weight

0.31 kg

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

5.2 cm

Package 1 Width

11.0 cm

Package 1 Length

13.5 cm

Package 1 Weight

327.0 g

Warranty

18 months

Document Links

Datasheet