Range
TeSys
Product name
TeSys LRD TeSys Deca
Product or component type
Differential thermal overload relay
Device short name
LRD
Relay application
Motor protection
Product compatibility
LC1D95 LC1D80
Network type
DC AC
Thermal overload class
Class 10A conforming to IEC 60947-4-1
Thermal protection adjustment range
80…104 A
[Ui] rated insulation voltage
Power circuit: 600 V conforming to CSA Power circuit: 600 V conforming to UL Power circuit: 750 V conforming to IEC 60947-4-1
Network frequency
0...400 Hz
Mounting support
Plate Rail
Tripping threshold
1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Auxiliary contact composition
1 NO + 1 NC
[Ith] conventional free air thermal current
5 A for signalling circuit
Permissible current
0.72 A at 500 V AC-15 for signalling circuit 0.06 A at 440 V DC-13 for signalling circuit
[Ue] rated operational voltage
1000 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating
4 A gG for signalling circuit 4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage
6 kV
Phase failure sensitivity
Tripping current 130 % of Ir on two phase, the last one at 0
Control type
Red push-button: stop Blue push-button: reset
Temperature compensation
-20…60 °C
Connections - terminals
Power circuit: screw clamp terminals 1 cable(s) 4…35 mm² flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 4…35 mm² flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 4…35 mm² solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end
Tightening torque
Control circuit: 1.7 N.m - on screw clamp terminals Power circuit: 9 N.m - on screw clamp terminals
height
123 mm
Net weight
1 kg
Climatic withstand
conforming to IACS E10
IP degree of protection
IP20 conforming to IEC 60529
Ambient air temperature for operation
-20…60 °C without derating conforming to IEC 60947-4-1
Ambient air temperature for storage
-60…70 °C
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations: 6 Gn conforming to IEC 60068-2-6 Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
Dielectric strength
2.2 kV at 50 Hz conforming to IEC 60947-1
standards
EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4 GB/T 14048.5 EN 50495
product certifications
IEC UL CSA CCC EAC ATEX INERIS UKCA
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
20.0 cm
Package 1 Width
13.55 cm
Package 1 Length
10.25 cm
Package 1 Weight
1.015 kg
Warranty
18 months
Datasheet