TeSys Deca contactor, 4-pole (4NO), for non-inductive load applications up to 125A/1000V AC-1. It provides a 24V DC coil, power connection by screw terminals, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (96mm width), DIN-rail mounting or screw fixing. Without build-in auxiliary contacts, front mounting auxiliary contact blocks can be added (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Range
TeSys
Range of product
TeSys Deca
Product or component type
Contactor
Device short name
LP1D
contactor application
Resistive load
utilisation category
AC-1 AC-3 AC-3e AC-4
Poles description
4P
[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz Power circuit: <= 300 V DC
[Ie] rated operational current
125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit 80 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 80 A (at <60 °C) at <= 440 V AC AC-3e for power circuit 55 A (at <60 °C) at <= 400 V AC AC-4 for power circuit
[Uc] control circuit voltage
24 V DC
Compatibility code
LP1D
Pole contact composition
4 NO
Contact compatibility
M4
Protective cover
Without
[Ith] conventional free air thermal current
125 A (at 60 °C) for power circuit
Irms rated making capacity
1100 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
135 A 40 °C - 10 min for power circuit 320 A 40 °C - 1 min for power circuit 640 A 40 °C - 10 s for power circuit 990 A 40 °C - 1 s for power circuit
Associated fuse rating
200 A gG at <= 690 V coordination type 1 for power circuit 160 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
0.8 mOhm - Ith 125 A 50 Hz for power circuit
Power dissipation per pole
12.5 W AC-1 5.1 W AC-3 5.1 W AC-3e
[Ui] rated insulation voltage
Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Power circuit: 1000 V conforming to IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability
4 Mcycles
Electrical durability
0.8 Mcycles 125 A AC-1 at Ue <= 440 V
Control circuit type
DC DC standard
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.1...0.3 Uc (-40…70 °C):drop-out DC 0.85...1.1 Uc (-40…55 °C):operational DC 1...1.1 Uc (55…70 °C):operational DC
Inrush power in W
22 W (at 20 °C)
Hold-in power consumption in W
22 W at 20 °C
Operating time
6...20 ms opening 20...35 ms closing
Time constant
75 ms
Maximum operating rate
3600 cyc/h 60 °C
Connections - terminals
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid Power circuit: connector 1 4…50 mm² - cable stiffness: flexible without cable end Power circuit: connector 2 4…25 mm² - cable stiffness: flexible without cable end Power circuit: connector 1 4…50 mm² - cable stiffness: flexible with cable end Power circuit: connector 2 4…16 mm² - cable stiffness: flexible with cable end Power circuit: connector 1 4…50 mm² - cable stiffness: solid Power circuit: connector 2 4…25 mm² - cable stiffness: solid Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end
Tightening torque
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm Power circuit: 12 N.m - on connector hexagonal screw head 4 mm Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2
mounting support
Rail Plate
Standards
CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
product certifications
BV CCC CSA DNV EAC GL LROS (Lloyds register of shipping) UL UKCA
IP degree of protection
IP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device
-40…60 °C 60…70 °C with derating
Operating altitude
0...3000 m
Fire resistance
850 °C conforming to IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations contactor open (2 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (8 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)
height
127 mm
Width
96 mm
Depth
181 mm
Net weight
2.685 kg
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
11.000 cm
Package 1 Width
13.500 cm
Package 1 Length
20.500 cm
Package 1 Weight
2.712 kg
Unit Type of Package 2
S02
Number of Units in Package 2
2
Package 2 Height
15.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
5.658 kg
Unit Type of Package 3
P06
Number of Units in Package 3
32
Package 3 Height
75.000 cm
Package 3 Width
80.000 cm
Package 3 Length
60.000 cm
Package 3 Weight
98.528 kg
Warranty
18 months
Datasheet
Technical Data