LA4DWB

INTERFACE MODULE

Trade Price

£73.36

Per

1

Unit

EA

Pack Quantity

1

LA4DWB

Information

TeSys Deca low signal interface module, for control of contactors LC.D09-D115 (3P). Static relay interface controlled by a 24V DC input signal. To be used with contactors with 24-250V AC coils (B7 to U7), for contactors LC.D80-D115 the use is limited to 100-250V AC coils (F7 to U7). To be mounted on a coil wiring adapter LAD4BB for contactors LC.D09-D38, LAD4BB3 for contactors LC.D40A-D80A, and directly on contactors LC.D80-D115. Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys

Device short name

LA4D

Poles description

3P

Product or component type

Interface module

Product compatibility

LC1D09...D115

Mounting mode

Top mounted

Technology type

Solid state

[Us] rated supply voltage

24 V DC

Control circuit voltage limits

5...30 V at 20 °C DC

[Ui] rated insulation voltage

250 V - for control circuit conforming to IEC 60947-5-1

Connections - terminals

Control circuit: connector 1 cable(s) 1…2.5 mm²flexible with cable end Control circuit: connector 1 cable(s) 1…2.5 mm²flexible without cable end Control circuit: connector 1 cable(s) 1…2.5 mm²solid with cable end Control circuit: connector 1 cable(s) 1…2.5 mm²solid without cable end Control circuit: connector 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: connector 2 cable(s) 1…2.5 mm²flexible without cable end Control circuit: connector 2 cable(s) 1…2.5 mm²solid with cable end Control circuit: connector 2 cable(s) 1…2.5 mm²solid without cable end

[Ue] rated operational voltage

Control circuit: 24...250 V AC

Current consumption

8.5...15 mA 20 °C

Current state 0 guaranteed

<= 2 mA

Voltage state 0 guaranteed

< 2.4 V

Voltage state 1 guaranteed

5 V

Electrical durability

20 Mcycles at 240 V

Local signalling

LED indicator

height

19 mm

Net weight

0.045 kg

standards

IEC 60255-5

product certifications

CSA UL

[Ith] conventional free air thermal current

8 A 50 °C

Protection type

Built-in by diode

IP degree of protection

IP2X conforming to IEC 60529

Ambient air temperature for operation

-25…55 °C

Permissible ambient air temperature around the device

-25…70 °C

Ambient air temperature for storage

-40…80 °C

Heat dissipation

0.4 W for control circuit

Immunity to microbreaks

1 ms

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

4.8 cm

Package 1 Width

4.8 cm

Package 1 Length

5.0 cm

Package 1 Weight

56.0 g

Unit Type of Package 2

S02

Number of Units in Package 2

70

Package 2 Height

15.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

4.22 kg

Warranty

18 months

Document Links

Datasheet

Technical Data