Trade Price
£72.35
Per
1
Unit
EA
Pack Quantity
1
TeSys GV motor circuit breaker, 3 poles (3P), 6.3A/690V, for 3-phase motor applications 2.2kW@400V. It provides a thermal-magnetic protection with a thermal setting range 4-6.3A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
Range
TeSys Deca
Product name
TeSys GV2 TeSys Deca
Product or component type
Motor circuit breaker
Device short name
GV2ME
Device application
Motor protection
Trip unit technology
Thermal-magnetic
Poles description
3P
Network type
AC
Utilisation category
Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1
Network frequency
50/60 Hz conforming to IEC 60947-4-1
Fixing mode
35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate)
Motor power kW
2.2 kW at 400/415 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz 4 kW at 690 V AC 50/60 Hz
Breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control type
Push-button
[In] rated current
6.3 A
Thermal protection adjustment range
4…6.3 A conforming to IEC 60947-4-1
Magnetic tripping current
78 A
[Ith] conventional free air thermal current
6.3 A conforming to IEC 60947-4-1
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
Phase failure sensitivity
Yes conforming to IEC 60947-4-1
Suitability for isolation
Yes conforming to IEC 60947-1 § 7-1-6
Power dissipation per pole
2.5 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles for AC-3 at 415 V In
Rated duty
Continuous conforming to IEC 60947-4-1
Tightening torque
1.7 N.m - on screw clamp terminal
Width
45 mm
height
89 mm
Depth
78.5 mm
Net weight
0.26 kg
Colour
Dark grey
standards
EN/IEC 60947-2 EN/IEC 60947-4-1
product certifications
CCC UL CSA EAC ATEX LROS (Lloyds register of shipping) BV RINA DNV-GL UKCA
IK degree of protection
IK04
IP degree of protection
IP20 conforming to IEC 60529
Climatic withstand
conforming to IACS E10
Ambient air temperature for storage
-40…80 °C
Fire resistance
960 °C conforming to IEC 60695-2-11
Ambient air temperature for operation
-20…60 °C
Mechanical robustness
Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz
Operating altitude
2000 m
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
4.500 cm
Package 1 Width
8.500 cm
Package 1 Length
9.500 cm
Package 1 Weight
277.000 g
Unit Type of Package 2
S02
Number of Units in Package 2
24
Package 2 Height
15.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
6.896 kg
Unit Type of Package 3
P06
Number of Units in Package 3
384
Package 3 Height
75.000 cm
Package 3 Width
80.000 cm
Package 3 Length
60.000 cm
Package 3 Weight
118.336 kg
Warranty
18 months