GV2L20

MOTOR CIRCUIT BREAKER

Trade Price

£101.29

Per

1

Unit

EA

Pack Quantity

1

GV2L20

Information

TeSys GV motor circuit breaker, 3 poles (3P), 18A/690V, for 3-phase motor applications 7.5kW@400V. It provides a magnetic protection with a tripping level at 13xIn, high breaking capacity Icu 50kA@400V. Connection by screw clamp terminals. Start-stop control by rotary handle guaranteed for 100 000 cycles AC-3. To complete motor protection, use in association with a thermal overload relay LRD21 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys Deca

Product name

TeSys GV2 TeSys Deca

Product or component type

Motor circuit breaker

Device short name

GV2L

Device application

Motor protection

Trip unit technology

Magnetic

Poles description

3P

Network type

AC

Utilisation category

Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1

Network frequency

50/60 Hz conforming to IEC 60947-2

Fixing mode

35 mm symmetrical DIN rail: clipped Panel: screwed (with 2 x M4 screws)

Motor power kW

7.5 kW at 400/415 V AC 50/60 Hz 9 kW at 500 V AC 50/60 Hz 15 kW at 690 V AC 50/60 Hz

Breaking capacity

100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service short-circuit breaking capacity

100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

Control type

Rotary handle

[In] rated current

18 A

Magnetic tripping current

223 A

[Ith] conventional free air thermal current

18 A conforming to IEC 60947-4-1

[Ue] rated operational voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

[Ui] rated insulation voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-2

Suitability for isolation

Yes conforming to IEC 60947-1 § 7-1-6

Power dissipation per pole

1.8 W

Mechanical durability

100000 cycles

Electrical durability

100000 cycles for AC-3 at 415 V In

Rated duty

Continuous conforming to IEC 60947-4-1

Tightening torque

1.7 N.m - on screw clamp terminal

Width

45 mm

height

89 mm

Depth

97 mm

Net weight

0.33 kg

Colour

Dark grey

standards

EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1

product certifications

CCC UL CSA EAC LROS (Lloyds register of shipping) BV RINA DNV-GL UKCA IECEE CB Scheme

IK degree of protection

IK04

IP degree of protection

IP20 conforming to IEC 60529

Climatic withstand

conforming to IACS E10

Ambient air temperature for storage

-40…80 °C

Fire resistance

960 °C conforming to IEC 60695-2-11

Ambient air temperature for operation

-20…60 °C

Mechanical robustness

Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz

Operating altitude

2000 m

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

9.300 cm

Package 1 Width

4.600 cm

Package 1 Length

10.000 cm

Package 1 Weight

330.000 g

Unit Type of Package 2

S02

Number of Units in Package 2

20

Package 2 Height

15.000 cm

Package 2 Width

30.000 cm

Package 2 Length

40.000 cm

Package 2 Weight

6.930 kg

Warranty

18 months

Document Links

Datasheet

Technical Data