LTMR27MFM

CONTROLLER MODBUS 1.35 27A 115 23

Trade Price

£511.50

Per

1

Unit

EA

Pack Quantity

1

LTMR27MFM

Information

TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. It manages most critical processes while reducing downtime and increasing productivity as well as predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This motor management system is also a flexible system that supports six communication protocols which are Modbus™, CANopen, DeviceNet™, Profibus™, Ethernet/IP, and Modbus/TCP. TeSys T motor management system consist of several components which include the LTMR controller, the expansion module, HMI and software along with several accessories. The LTMR controller is the main component of the system that manages the basic functions. This includes the measurement of the ground current, motor temperature, three phase current of the motor, the controller also includes logic inputs and outputs which is used in fault management. The expansion module is directly connected to the controller and provides additional inputs as well as measure the voltage between the phases which allow the controller the monitor additional functions. TeSys T is highly reliable and has a very long product life thanks to a state-of-the-art component selection, to the all in one design and to the advanced electronic protection. TeSys T can be integrated in many different types of harsh environment such as dusty atmospheres, marine applications, high vibration applications and corrosive atmospheres and is used in Metal/Mining/Mineral, Oil & Gas, Water Wastewater. This is a TeSys T LTMR controller that measure current range of 1.35-27A with a supply voltage of 100-240 Vac and uses CANopen as the communication protocol. This controller measures temperature, phase current, imbalance current, average current and earth-fault current. The dimensions of this device are 61 mm (H) X 91 mm (W) X 122.5 mm (D) and it weighs 0.53 kg.

Technical Specifications

Range

TeSys

Product name

TeSys T

Device short name

LTMR

Product or component type

Motor controller

Device application

Equipment monitoring and control

Measurement current

1.35…27 A

[Us] rated supply voltage

100...240 V AC 50/60 Hz

Current consumption

8...62.8 mA

Supply voltage limits

93.5…264 V AC

Communication port protocol

Modbus

Bus type

Modbus 2-wire RS 485 interface, addressing 1...247, transmission rate 1.2...19.2 kbit/s, RJ45 with 2 shielded twisted pairs Modbus 2-wire RS 485 interface, addressing 1...247, transmission rate 1.2...19.2 kbit/s, terminal block with 2 shielded twisted pairs

[Ui] rated insulation voltage

690 V conforming to EN/IEC 60947-1 690 V conforming to CSA C22.2 No 14 690 V conforming to UL 508

[Uimp] rated impulse withstand voltage

4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 0.8 kV communication circuit conforming to EN/IEC 60947-4-1

Short-circuit withstand

100 kA conforming to EN/IEC 60947-4-1

Associated fuse rating

4 A gG for output 0.5 A gG for control circuit

Protection type

Reverse polarity protection Overload (long time) Earth-leakage protection Phase unbalance Overload Load fluctuation Phase failure Power factor variation Thermal protection Locked rotor Thermal overload protection

Network and machine diagnosis type

Fault recording Starting current and time Remaining operating time before overload tripping Waiting time after overload tripping Motor control command recording Event recording Trip history information Running hours counter/operating time Phase fault and earth fault trip counters Trip context information

Logic input number

6

Input current

3.1 mA at 100 V 7.5 mA at 240 V

Current state 0 guaranteed

Logic input: 0...40 V and <= 15 mA for 25 ms

Current state 1 guaranteed

Logic input: 79...264 V and >= 2 mA for 25 ms

maximum output switching frequency

2 Hz

Load current

5 A at 250 V AC for logic output 5 A at 30 V DC for logic output

Permissible power

480 VA (AC-15), Ie = 2 A, 500000 cycles (output) 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)

Maximum operating rate

1800 cyc/h

Contacts type and composition

1 NO + 1 NC fault signal 3 NO

Metering type

Temperature Phase current I1, I2, I3 RMS Average current Iavg Earth-fault current Imbalance current

Measurement accuracy

5...15 % earth fault current internal measurement 1 % voltage (100...830 V) 3 % power factor 5 % earth fault current external measurement +/- 30 min/year internal clock 0,02 temperature 1 % current 5 % active and reactive power

Overvoltage category

III

Connection pitch

5.08 mm

Connections - terminals

Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible with cable end Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) solid without cable end Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) flexible with cable end Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) solid without cable end

Tightening torque

Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm

Pollution degree

3

Electromagnetic compatibility

Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5 Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5

Width

91 mm

height

61 mm

Depth

122.5 mm

Net weight

0.53 kg

Web services

Web server

Compatibility code

LTMR

standards

CSA C22.2 No 14 UL 508 EN 60947-4-1 IEC 60947-4-1 IACS E10

product certifications

RMRoS LROS (Lloyds register of shipping) RINA ABS CCC EAC UL GL NOM DNV KERI ATEX BV CSA C-Tick

Protective treatment

12 x 24 hour cycles conforming to EN/IEC 60068-2-30 48 h conforming to EN/IEC 60070-2-11 TH conforming to EN/IEC 60068

Fire resistance

650 °C conforming to EN/IEC 60695-2-12 960 °C conforming to UL 94

Ambient air temperature for operation

-20…60 °C

Ambient air temperature for storage

-40…80 °C

Operating altitude

<= 2000 m without derating

Mechanical robustness

Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27

IP degree of protection

IP20

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

7.2 cm

Package 1 Width

10.0 cm

Package 1 Length

13.6 cm

Package 1 Weight

525.0 g

Unit Type of Package 2

S02

Number of Units in Package 2

10

Package 2 Height

15.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

5.604 kg

Warranty

18 months

Document Links