LC2D32B7

REVERSING CONT 1NO + 1NC 32A 24V 50/60H

Trade Price

£333.65

Per

1

Unit

EA

Pack Quantity

1

LC2D32B7

Information

TeSys D reversing contactor, 3 poles (3NO), for motor control applications up to 32A/690V AC-3 (15kW@400V). It provides 24V 50/60Hz AC coils, 2NO+2NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys TeSys Deca

Product name

TeSys D TeSys Deca

Product or component type

Reversing contactor

Device short name

LC2D

contactor application

Resistive load Motor control

utilisation category

AC-1 AC-3 AC-3e

Device presentation

Preassembled with reversing power busbar

Poles description

3P

power pole contact composition

3 NO

[Ue] rated operational voltage

Power circuit: <= 690 V AC 25...400 Hz Power circuit: <= 300 V DC

[Ie] rated operational current

32 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit 32 A (at <60 °C) at <= 440 V AC AC-3e for power circuit

Motor power kW

7.5 kW at 220...230 V AC 50...60 Hz 15 kW at 380...400 V AC 50...60 Hz 15 kW at 415 V AC 50...60 Hz 15 kW at 440 V AC 50...60 Hz 18.5 kW at 500 V AC 50...60 Hz 18.5 kW at 660...690 V AC 50...60 Hz

motor power HP (UL / CSA)

2 hp at 115 V AC 60 Hz for 1 phase motors 5 hp at 230/240 V AC 60 Hz for 1 phase motors 10 hp at 200/208 V AC 60 Hz for 3 phases motors 10 hp at 230/240 V AC 60 Hz for 3 phases motors 20 hp at 460/480 V AC 60 Hz for 3 phases motors 30 hp at 575/600 V AC 60 Hz for 3 phases motors

Control circuit type

AC at 50/60 Hz

[Uc] control circuit voltage

24 V AC 50/60 Hz

Auxiliary contact composition

1 NO + 1 NC

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Overvoltage category

III

[Ith] conventional free air thermal current

10 A (at 60 °C) for signalling circuit 50 A (at 60 °C) for power circuit

Irms rated making capacity

140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 550 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity

550 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current

60 A 40 °C - 10 min for power circuit 138 A 40 °C - 1 min for power circuit 260 A 40 °C - 10 s for power circuit 430 A 40 °C - 1 s for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit

Associated fuse rating

10 A gG for signalling circuit conforming to IEC 60947-5-1 63 A gG at <= 690 V coordination type 1 for power circuit 63 A gG at <= 690 V coordination type 2 for power circuit

Average impedance

2 mOhm - Ith 50 A 50 Hz for power circuit

[Ui] rated insulation voltage

Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified

Electrical durability

1.65 Mcycles 32 A AC-3 at Ue <= 440 V 1.4 Mcycles 50 A AC-1 at Ue <= 440 V 1.65 Mcycles 32 A AC-3e at Ue <= 440 V

Power dissipation per pole

2 W AC-3 5 W AC-1 2 W AC-3e

Front cover

With

Interlocking type

Mechanical

mounting support

Rail Plate

Standards

CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 IEC 60335-1

product certifications

UL CSA RINA GOST CCC DNV LROS (Lloyds register of shipping) GL BV UKCA

Connections - terminals

Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm²flexible without cable end Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 1…10 mm²flexible with cable end Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm²flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm²solid Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²solid

Tightening torque

Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Operating time

12...22 ms closing 4...19 ms opening

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability

15 Mcycles

Maximum operating rate

3600 cyc/h 60 °C

Coil technology

Without built-in suppressor module

Control circuit voltage limits

0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz

Inrush power in VA

70 VA 60 Hz cos phi 0.75 (at 20 °C) 70 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA

7.5 VA 60 Hz cos phi 0.3 (at 20 °C) 7 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation

2…3 W at 50/60 Hz

Auxiliary contacts type

type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1

Signalling circuit frequency

25...400 Hz

Minimum switching current

5 mA for signalling circuit

Minimum switching voltage

17 V for signalling circuit

Non-overlap time

1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact

Insulation resistance

> 10 MOhm for signalling circuit

IP degree of protection

IP20 front face conforming to IEC 60529

Climatic withstand

conforming to IACS E10 conforming to IEC 60947-1 Annex Q category D

Protective treatment

TH conforming to IEC 60068-2-30

Pollution degree

3

Ambient air temperature for operation

-40…60 °C 60…70 °C with derating

Ambient air temperature for storage

-60…80 °C

Operating altitude

0...3000 m

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V1 conforming to UL 94

Mechanical robustness

Vibrations contactor open: 2 Gn, 5...300 Hz Vibrations contactor closed: 4 Gn, 5...300 Hz Shocks contactor closed: 15 Gn for 11 ms Shocks contactor open: 8 Gn for 11 ms

height

85 mm

Width

90 mm

Depth

92 mm

Net weight

0.797 kg

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

11.5 cm

Package 1 Width

12.5 cm

Package 1 Length

14.0 cm

Package 1 Weight

952.0 g

Unit Type of Package 2

S02

Number of Units in Package 2

5

Package 2 Height

15.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

5.09 kg

Warranty

18 months

Document Links

Datasheet

Technical Data