Trade Price
POA
Per
1
Unit
Pack Quantity
This DC choke is used to reduce current harmonics in order to comply with standard IEC 61000-3-12. It is compatible with Altivar 61 and Altivar 71. It provides IP 20 degree of protection.
Product or component type
DC choke
Range compatibility
Altivar 61 Altivar 71
Device application
Reduction of current harmonics
Value of inductance
3.9 mH
[In] rated current
10.7 A
Thermal losses
27 W
Product compatibility
ATV61HU40N4 ATV71HU40N4 ATV71WU40N4 ATV71PU40N4Z
Electrical connection
Earth circuit terminal, connection capacity: 10 mm² (AWG 6) Power supply terminal, connection capacity: 2.5 mm² (AWG 12)
Network number of phases
3 phases
Supply frequency
50...60 Hz
Maximum voltage drop at rated load
6 %
Max current
1.65 x nominal current (duration = 60 s)
Tightening torque
1.2...1.4 N.m for earth circuit 0.4...0.6 N.m for power supply
height
134 mm
Width
96 mm
Depth
115 mm
Net weight
1.65 kg
IP degree of protection
IP20
Relative humidity
0…95 %
Ambient air temperature for operation
50…60 °C (with current derating 2.2 % per °C) -10…50 °C (without current derating)
Ambient air temperature for storage
-40…65 °C
Operating altitude
<= 1000 m without current derating 1000...3000 m with current derating 1 % per 100 m
Warranty
18 months