Trade Price
POA
Per
1
Unit
EA
Pack Quantity
1
This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It features 3 built-in RJ45 communication ports as standard, 1 Ethernet port, 2 serial ports. It works at a rated supply voltage from 380V to 440V AC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 315kW for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 250kW for applications requiring significant overload (up to 150%). It weighs 400kg and its dimensions are, 600mm wide, 2150mm high, 605mm deep. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. Accessories (fan kit, graphic display terminal) and options (I/O expansion modules, communication modules, EMC input filters) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on the floor. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.
Range of product
Altivar Process ATV600
Product or component type
Variable speed drive
Product specific application
Process and utilities
Device short name
ATV630
Variant
Standard version
Product destination
Asynchronous motors Synchronous motors
EMC filter
Integrated with 150 m conforming to EN/IEC 61800-3 category C3
IP degree of protection
IP21 conforming to IEC 61800-5-1 IP21 conforming to IEC 60529
[Us] rated supply voltage
380...440 V - 15...10 %
Type of cooling
Forced convection
Supply frequency
50...60 Hz - 5...5 %
Motor power kW
315 kW (normal duty) 250 kW (heavy duty)
Line current
488 A at 400 V (normal duty) 391 A at 400 V (heavy duty) 566 A at 380 V (normal duty) 453 A at 380 V (heavy duty)
Prospective line Isc
50 kA
Apparent power
372 kVA at 440 V (normal duty) 298 kVA at 440 V (heavy duty)
Continuous output current
590 A at 2.5 kHz for normal duty 477 A at 2.5 kHz for heavy duty
Asynchronous motor control profile
Constant torque standard Variable torque standard Optimized torque mode
Synchronous motor control profile
Permanent magnet motor Synchronous reluctance motor
Speed drive output frequency
0.1…500 Hz
Nominal switching frequency
2.5 kHz
Switching frequency
2.5...8 kHz with derating factor 2...8 kHz adjustable
Safety function
STO (safe torque off) SIL 3
Discrete input logic
Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1) Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)
Communication port protocol
Ethernet Modbus serial Modbus TCP
Option card
Slot A: communication module, Profibus DP V1 Slot A: communication module, PROFINET Slot A: communication module, DeviceNet Slot A: communication module, Modbus TCP/EtherNet/IP Slot A: communication module, CANopen daisy chain RJ45 Slot A: communication module, CANopen SUB-D 9 Slot A: communication module, CANopen screw terminals Slot A/slot B: digital and analog I/O extension module Slot A/slot B: output relay extension module Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link Communication module, BACnet MS/TP Communication module, Ethernet Powerlink
Mounting mode
Floor-standing
Maximum transient current
649 A during 60 s (normal duty) 716 A during 60 s (heavy duty)
Network number of phases
3 phases
Discrete output number
0
Discrete output type
Relay outputs R1A, R1B, R1C 250 V AC 3000 mA Relay outputs R1A, R1B, R1C 30 V DC 3000 mA Relay outputs R2A, R2C 250 V AC 5000 mA Relay outputs R2A, R2C 30 V DC 5000 mA Relay outputs R3A, R3C 250 V AC 5000 mA Relay outputs R3A, R3C 30 V DC 5000 mA
Output voltage
<= power supply voltage
Permissible temporary current boost
1.1 x In during 60 s (normal duty) 1.5 x In during 60 s (heavy duty)
Motor slip compensation
Automatic whatever the load Not available in permanent magnet motor law Can be suppressed Adjustable
Acceleration and deceleration ramps
Linear adjustable separately from 0.01...9999 s
Physical interface
Ethernet 2-wire RS 485
Braking to standstill
By DC injection
Protection type
Thermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
Transmission rate
10, 100 Mbits 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Frequency resolution
Display unit: 0.1 Hz Analog input: 0.012/50 Hz
Transmission frame
RTU
Electrical connection
Control: removable screw terminals 0.5...1.5 mm² Line side: M12 bar - 3 cables 3 x 185 mm² maximum per phase (normal duty) Line side: M12 bar - 4 cables 3 x 120 mm² maximum per phase (normal duty) Motor: M12 bar - 3 cables 3 x 185 mm² maximum per phase (normal duty) Motor: M12 bar - 4 cables 3 x 120 mm² maximum per phase (normal duty) Line side: M12 bar - 3 cables 3 x 185 mm² maximum per phase (heavy duty) Line side: M12 bar - 4 cables 3 x 120 mm² maximum per phase (heavy duty) Motor: M12 bar - 3 cables 3 x 185 mm² maximum per phase (heavy duty) Motor: M12 bar - 4 cables 3 x 120 mm² maximum per phase (heavy duty) Line side: M12 bar - 3 cables 3 x 150 mm² minimum per phase (normal duty) Line side: M12 bar - 4 cables 3 x 95 mm² minimum per phase (normal duty) Motor: M12 bar - 2 cables 3 x 185 mm² minimum per phase (normal duty) Motor: M12 bar - 3 cables 3 x 120 mm² minimum per phase (normal duty) Line side: M12 bar - 2 cables 3 x 185 mm² minimum per phase (heavy duty) Line side: M12 bar - 3 cables 3 x 95 mm² minimum per phase (heavy duty) Motor: M12 bar - 2 cables 3 x 185 mm² minimum per phase (heavy duty) Motor: M12 bar - 3 cables 3 x 120 mm² minimum per phase (heavy duty)
Connector type
RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP RJ45 (on the remote graphic terminal) for Modbus serial
Data format
8 bits, configurable odd, even or no parity
Type of polarization
No impedance
Exchange mode
Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Number of addresses
1…247 for Modbus serial
Method of access
Slave Modbus TCP
Supply
External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
Local signalling
3 LEDs for local diagnostic 3 LEDs (dual colour) for embedded communication status 4 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage
Width
600 mm
height
2150 mm
Depth
605 mm
Net weight
400 kg
analogue input number
3
Analogue input type
AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
Discrete input number
8
Discrete input type
DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
Input compatibility
DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2 DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68 STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
analogue output number
2
Analogue output type
Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits Software-configurable current DQ-, DQ+: 30 V DC Software-configurable current DQ-, DQ+: 100 mA
Sampling duration
2 ms +/- 0.5 ms (DI1...DI4) - discrete input 5 ms +/- 1 ms (DI5, DI6) - discrete input 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input 10 ms +/- 1 ms (AO1) - analog output
Accuracy
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Linearity error
AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AO1, AO2: +/- 0.2 % for analog output
Relay output number
3
Relay output type
Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Refresh time
Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Minimum switching current
Relay output R1, R2, R3: 5 mA at 24 V DC
Maximum switching current
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Isolation
Between power and control terminals
Maximum output frequency
500 kHz
Maximum input current
566.0 A
Variable speed drive application selection
Building - HVAC compressor centrifugal Food and beverage processing other application Mining mineral and metal fan Mining mineral and metal pump Oil and gas fan Water and waste water other application Building - HVAC screw compressor Food and beverage processing pump Food and beverage processing fan Food and beverage processing atomization Oil and gas electro submersible pump (ESP) Oil and gas water injection pump Oil and gas jet fuel pump Oil and gas compressor for refinery Water and waste water centrifuge pump Water and waste water positive displacement pump Water and waste water electro submersible pump (ESP) Water and waste water screw pump Water and waste water lobe compressor Water and waste water screw compressor Water and waste water compressor centrifugal Water and waste water fan Water and waste water conveyor Water and waste water mixer
Motor power range AC-3
250…500 kW at 380…440 V 3 phases
Quantity per set
1
Enclosure mounting
Floor-standing
Insulation resistance
> 1 MOhm 500 V DC for 1 minute to earth
Noise level
70 dB
Power dissipation in W
7810 W, switching frequency 2.5 kHz (normal duty) 5700 W, switching frequency 2.5 kHz (heavy duty)
Volume of cooling air
1300 m3/h
Operating position
Vertical +/- 10 degree
Maximum THDI
<48 % full load conforming to IEC 61000-3-12
Electromagnetic compatibility
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Pollution degree
2
Vibration resistance
1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Relative humidity
5…95 % without condensation conforming to IEC 60068-2-3
Ambient air temperature for operation
-15…40 °C (without derating) 40…50 °C (with derating factor)
Ambient air temperature for storage
-40…70 °C
Operating altitude
<= 1000 m without derating 1000...4800 m with current derating 1 % per 100 m
product certifications
ATEX EAC C-Tick
Marking
CE
standards
EN/IEC 60204-1 EN/IEC 61800-2 EN/IEC 61800-3 EN/IEC 61800-5-1
Overvoltage category
III
Regulation loop
Adjustable PID regulator
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
217.5 cm
Package 1 Width
111.0 cm
Package 1 Length
120.0 cm
Package 1 Weight
462.0 kg
Warranty
18 months
Datasheet