Trade Price
POA
Per
1
Unit
EA
Pack Quantity
7
Altivar Machine ATV12 is an offer of variable speed drives for commercial equipment and simple machines. It works at a rated power up to 1.5kW / 2hp and a rated voltage from 200V to 240V AC. It is designed with heatsink for normal environments and fan-cooled enclosure. It has advanced PID and catch on the fly functions, basic cabling, and easy motor control setting. Based on the needs, it can be delivered without heatsink, with embedded EMC filter, or as standard version. The Altivar 12 drive integrates as standard the Modbus communication protocol. This Altivar Machine ATV12 is designed for simple applications, in industry, commercial machines and HVAC machines such as conveyors, pumps, extractors, access barriers and treadmills. It conforms to IEC, UL and other international standards. SoMove software compatibility enables saving and transfering of configurations to spare drive, reducing maintenance downtime. It is sold in lot of 7. It features an optimized application of power and torque for ventilation and pumping applications, this allows up to 30% energy savings. The ATV12 range meets basic machine requirements united with simplicity.
Range of product
Altivar 12
Product or component type
Variable speed drive
Product specific application
Simple machine
Mounting mode
Cabinet mount
Communication port protocol
Modbus
Supply frequency
50/60 Hz +/- 5 %
[Us] rated supply voltage
200...240 V - 15...10 %
Nominal output current
7.5 A
Motor power hp
2 hp
Motor power kW
1.5 kW
EMC filter
Integrated
IP degree of protection
IP20
Discrete input number
4
Discrete output number
2
analogue input number
1
analogue output number
1
Relay output number
1
Physical interface
2-wire RS 485
Connector type
1 RJ45
Continuous output current
7.5 A at 4 kHz
Method of access
Server Modbus serial
Speed drive output frequency
0.5…400 Hz
Speed range
1…20
Sampling duration
20 ms, tolerance +/- 1 ms for logic input 10 ms for analogue input
Linearity error
+/- 0.3 % of maximum value for analogue input
Frequency resolution
Analog input: converter A/D, 10 bits Display unit: 0.1 Hz
Time constant
20 ms +/- 1 ms for reference change
Transmission rate
9.6 kbit/s 19.2 kbit/s 38.4 kbit/s
Transmission frame
RTU
Number of addresses
1…247
Data format
8 bits, configurable odd, even or no parity
Communication service
Read holding registers (03) 29 words Write single register (06) 29 words Write multiple registers (16) 27 words Read/write multiple registers (23) 4/4 words Read device identification (43)
Type of polarization
No impedance
4 quadrant operation possible
False
Asynchronous motor control profile
Sensorless flux vector control Voltage/frequency ratio (V/f) Quadratic voltage/frequency ratio
Maximum output frequency
4 kHz
Transient overtorque
150…170 % of nominal motor torque depending on drive rating and type of motor
Acceleration and deceleration ramps
Linear from 0 to 999.9 s S U
Motor slip compensation
Adjustable Preset in factory
Switching frequency
2...16 kHz adjustable 4...16 kHz with derating factor
Nominal switching frequency
4 kHz
Braking to standstill
By DC injection
Brake chopper integrated
False
Line current
17.8 A at 100 V (heavy duty) 14.9 A at 120 V (heavy duty)
Maximum input current
14.9 A
Maximum output voltage
240 V
Apparent power
3.6 kVA at 240 V (heavy duty)
Maximum transient current
11.2 A during 60 s (heavy duty) 12.4 A during 2 s (heavy duty)
Network frequency
50...60 Hz
Relative symmetric network frequency tolerance
5 %
Prospective line Isc
1 kA
Base load current at high overload
7.5 A
Power dissipation in W
Forced cooling: 72.0 W
With safety function Safely Limited Speed (SLS)
False
With safety function Safe brake management (SBC/SBT)
False
With safety function Safe Operating Stop (SOS)
False
With safety function Safe Position (SP)
False
With safety function Safe programmable logic
False
With safety function Safe Speed Monitor (SSM)
False
With safety function Safe Stop 1 (SS1)
False
With sft fct Safe Stop 2 (SS2)
False
With safety function Safe torque off (STO)
False
With safety function Safely Limited Position (SLP)
False
With safety function Safe Direction (SDI)
False
Protection type
Line supply overvoltage Line supply undervoltage Overcurrent between output phases and earth Overheating protection Short-circuit between motor phases Against input phase loss in three-phase Thermal motor protection via the drive by continuous calculation of I²t
tightening torque
1.2 N.m
insulation
Electrical between power and control
Quantity per set
Set of 7
Width
105 mm
height
142 mm
Depth
156.2 mm
Net weight
1.4 kg
Operating altitude
> 1000...2000 m with current derating 1 % per 100 m <= 1000 m without derating
Operating position
Vertical +/- 10 degree
product certifications
NOM CSA C-Tick UL GOST RCM KC
Marking
CE
standards
UL 508C UL 618000-5-1 EN/IEC 61800-5-1 EN/IEC 61800-3
Assembly style
With heat sink
Electromagnetic compatibility
Electrical fast transient/burst immunity test level 4 conforming to EN/IEC 61000-4-4 Electrostatic discharge immunity test level 3 conforming to EN/IEC 61000-4-2 Immunity to conducted disturbances level 3 conforming to EN/IEC 61000-4-6 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to EN/IEC 61000-4-3 Surge immunity test level 3 conforming to EN/IEC 61000-4-5 Voltage dips and interruptions immunity test conforming to EN/IEC 61000-4-11
Environmental class (during operation)
Class 3C3 according to IEC 60721-3-3 Class 3S2 according to IEC 60721-3-3
Maximum acceleration under shock impact (during operation)
150 m/s² at 11 ms
Maximum acceleration under vibrational stress (during operation)
10 m/s² at 13...200 Hz
Maximum deflection under vibratory load (during operation)
1.5 mm at 2...13 Hz
Volume of cooling air
16 m3/h
Overvoltage category
Class III
Regulation loop
Adjustable PID regulator
Electromagnetic emission
Radiated emissions environment 1 category C2 conforming to EN/IEC 61800-3 2...16 kHz shielded motor cable Conducted emissions with integrated EMC filter environment 1 category C1 conforming to EN/IEC 61800-3 2, 4, 8, 12 and 16 kHz shielded motor cable <5 m Conducted emissions with additional EMC filter environment 1 category C1 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <20 m Conducted emissions with additional EMC filter environment 1 category C2 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <50 m Conducted emissions with additional EMC filter environment 2 category C3 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <50 m Conducted emissions with integrated EMC filter environment 1 category C2 conforming to EN/IEC 61800-3 4...16 kHz shielded motor cable <5 m Conducted emissions with integrated EMC filter environment 1 category C2 conforming to EN/IEC 61800-3 2, 4, 8, 12 and 16 kHz shielded motor cable <10 m
Vibration resistance
1 gn (f = 13…200 Hz) conforming to EN/IEC 60068-2-6 1.5 mm peak to peak (f = 3…13 Hz) - drive unmounted on symmetrical DIN rail - conforming to EN/IEC 60068-2-6
Shock resistance
15 gn conforming to EN/IEC 60068-2-27 for 11 ms
Relative humidity
5…95 % without condensation conforming to IEC 60068-2-3 5…95 % without dripping water conforming to IEC 60068-2-3
Noise level
45 dB
Pollution degree
2
Ambient air transport temperature
-25…70 °C
Ambient air temperature for operation
-10…50 °C without derating 50…60 °C with current derating 2.2 % per °C
Ambient air temperature for storage
-25…70 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
20.000 cm
Package 1 Width
60.000 cm
Package 1 Length
40.000 cm
Package 1 Weight
1.720 kg
Unit Type of Package 2
BB1
Number of Units in Package 2
7
Package 2 Height
20.000 cm
Package 2 Width
40.000 cm
Package 2 Length
60.000 cm
Package 2 Weight
12.075 kg
Unit Type of Package 3
P06
Number of Units in Package 3
42
Package 3 Height
75.000 cm
Package 3 Width
60.000 cm
Package 3 Length
80.000 cm
Package 3 Weight
83.644 kg
Warranty
18 months
Datasheet