ATV212WD55N4C

ATV212 55KW 480V 3PH EMC B IP55

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

ATV212WD55N4C

Information

This Altivar 212 variable speed drive can feed 3-phase asynchronous motors. Its protection index is IP55 and it has a built-in EMC filter. It works at a rated power up to 55kW / 40hp and a rated voltage from 380V to 480V AC. Its design is based on eco-energy with a reduction in energy consumption of up to 70% compared to a conventional control system. Thanks to its cable temperature rise reduction technology, the Altivar 212 drive offers immediate, disturbance-free operation avoiding additional options such as a line choke or DC choke to deal with current harmonics. It weighs 88.4kg and its dimensions are, 362mm wide, 1000mm high, 364mm deep. It is specifically designed for the most common fluid management applications in tertiary sector buildings (HVAC) like heating, ventilation, air conditioning and pumping. It conforms to international standards IEC/EN 61800-5-1 and IEC/EN 61800-3 (immunity and conducted and radiated EMC emissions). It is also CE, UL, CSA, C-Tick and NOM certified. The Altivar 212 offers optional motor chokes which can increase the maximum cable lengths between the drive and the motor and limit disturbance at the motor terminals. It is designed to be mounted in vertical position (+/- 10 °) on a panel, thanks to 4 fixing holes. The Altivar 212 drive can easily be adapted to all building management systems thanks to its numerous functions and communication protocols integrated as standard, Modbus, METASYS N2, APOGEE FLN P1 and BACnet.

Technical Specifications

Device short name

ATV212

Product destination

Asynchronous motors

Network number of phases

3 phases

Motor power kW

55 kW

Motor power hp

75 hp

Supply voltage limits

323…528 V

Supply frequency

50...60 Hz - 5...5 %

Line current

102.7 A at 380 V 89 A at 480 V

Range of product

Altivar 212

Product or component type

Variable speed drive

Product specific application

Pumps and fans in HVAC

Communication port protocol

LonWorks APOGEE FLN BACnet METASYS N2 Modbus

[Us] rated supply voltage

380...480 V - 15...10 %

EMC filter

Class C1 EMC filter integrated

IP degree of protection

IP55 conforming to IEC 61800-5-1 IP55 conforming to IEC 60529

Apparent power

76.3 kVA at 380 V

Continuous output current

116 A at 380 V 116 A at 460 V

Maximum transient current

127.6 A for 60 s

Speed drive output frequency

0.5…200 Hz

Speed range

1…10

Speed accuracy

+/- 10 % of nominal slip 0.2 Tn to Tn

Local signalling

1 LED (red) for DC bus energized

Output voltage

<= power supply voltage

Isolation

Electrical between power and control

Type of cable

Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC

Electrical connection

VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14 L1/R, L2/S, L3/T: terminal 130 mm² (250 kcmil) U/T1, V/T2, W/T3: terminal 150 mm² (300 kcmil)

Tightening torque

0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) 16 N.m, 142 lb.in (L1/R, L2/S, L3/T) 41 N.m, 360 lb.in (U/T1, V/T2, W/T3)

Supply

Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection

Sampling duration

2 ms +/- 0.5 ms F discrete 2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 3.5 ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog

Response time

FM 2 ms, tolerance +/- 0.5 ms for analog output(s) FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)

Accuracy

+/- 0.6 % (VIA) for a temperature variation 60 °C +/- 0.6 % (VIB) for a temperature variation 60 °C +/- 1 % (FM) for a temperature variation 60 °C

Linearity error

VIA: +/- 0.15 % of maximum value for input VIB: +/- 0.15 % of maximum value for input FM: +/- 0.2 % for output

Analogue output type

FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits

Discrete output type

Configurable relay logic: (FLA, FLC) NO - 100000 cycles Configurable relay logic: (FLB, FLC) NC - 100000 cycles Configurable relay logic: (RY, RC) NO - 100000 cycles

Minimum switching current

3 mA at 24 V DC for configurable relay logic

Maximum switching current

5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) 5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)

Discrete input type

F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm

Discrete input logic

Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1) Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)

Dielectric strength

3535 V DC between earth and power terminals 5092 V DC between control and power terminals

Insulation resistance

>= 1 mOhm 500 V DC for 1 minute

Frequency resolution

Display unit: 0.1 Hz Analog input: 0.024/50 Hz

Communication service

Write multiple registers (16) 2 words maximum Write single register (06) Monitoring inhibitable Read holding registers (03) 2 words maximum Read device identification (43) Time out setting from 0.1 to 100 s

Option card

Communication card for LonWorks

Specific application

HVAC

Discrete output number

2

analogue input number

2

Analogue input type

VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits

analogue output number

1

Physical interface

2-wire RS 485

Connector type

1 RJ45 1 open style

Transmission rate

9600 bps or 19200 bps

Transmission frame

RTU

Number of addresses

1…247

Data format

8 bits, 1 stop, odd even or no configurable parity

Type of polarization

No impedance

Asynchronous motor control profile

Voltage/frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, 2 points Flux vector control without sensor, standard Voltage/frequency ratio, 5 points Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)

Torque accuracy

+/- 15 %

Transient overtorque

120 % of nominal motor torque +/- 10 % for 60 s

Acceleration and deceleration ramps

Linear adjustable separately from 0.01 to 3200 s Automatic based on the load

Motor slip compensation

Not available in voltage/frequency ratio motor control Automatic whatever the load Adjustable

Switching frequency

6...16 kHz adjustable 8...16 kHz with derating factor

Nominal switching frequency

8 kHz

Braking to standstill

By DC injection

Network frequency

47.5...63 Hz

Prospective line Isc

22 kA

Protection type

Overheating protection: drive Thermal power stage: drive Short-circuit between motor phases: drive Input phase breaks: drive Overcurrent between output phases and earth: drive Overvoltages on the DC bus: drive Break on the control circuit: drive Against exceeding limit speed: drive Line supply overvoltage and undervoltage: drive Line supply undervoltage: drive Against input phase loss: drive Thermal protection: motor Motor phase break: motor With PTC probes: motor

Width

362 mm

height

1000 mm

Depth

364 mm

Pollution degree

3 conforming to IEC 61800-5-1

Vibration resistance

1.5 mm (f= 3…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8

Shock resistance

15 gn for 11 ms conforming to IEC 60068-2-27

Environmental characteristic

Classes 3C1 conforming to IEC 60721-3-3 Classes 3S2 conforming to IEC 60721-3-3

Noise level

63.7 dB conforming to 86/188/EEC

Operating altitude

1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m <= 1000 m without derating

Relative humidity

5…95 % without condensation conforming to IEC 60068-2-3 5…95 % without dripping water conforming to IEC 60068-2-3

Ambient air temperature for operation

-10…40 °C (without derating) 40…50 °C (with derating factor)

Operating position

Vertical +/- 10 degree

product certifications

C-Tick CSA UL NOM 117

Marking

CE

standards

IEC 61800-3 environments 1 category C3 IEC 61800-3 environments 1 category C2 IEC 61800-5-1 IEC 61800-3 environments 1 category C1 IEC 61800-3 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C3 IEC 61800-3 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C1 IEC 61800-5-1 IEC 61800-3 IEC 61800-3 environments 1 category C2 EN 55011 group 1 class B IEC 61800-3 environments 2 category C3 EN 61800-3 category C1 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 1 category C3

Assembly style

With heat sink

Electromagnetic compatibility

Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11

Regulation loop

Adjustable PI regulator

Ambient air temperature for storage

-25…70 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

45 cm

Package 1 Width

44 cm

Package 1 Length

116 cm

Package 1 Weight

77 kg

Warranty

18 months

Document Links

Datasheet