This Altistart 22 soft starter can feed 3-phase asynchronous motors in supply line or delta connection. It has a rating of 140A and 230V to 440V, a rated power up to 75kW (400V to 440V in supply line) and up to 110kW (400V to 440V in motor delta connection). It is designed for simple and complex machines such as centrifugal and piston pumps, fans, screw compressors and material handling equipment. Slim form factor improves versatility; allows mounting in frames of any kind of machines. It features an Integrated bypass, this reduces noise and decreases heat dissipation. Compatibility with SoMove software allows configurations and settings to be easily transferred, meaning spares can be quickly installed. It provides smooth starting for your machinery, avoiding mechanical stresses and extending their service life.
Range of product
Altistart 22
Product or component type
Soft starter
Product destination
Asynchronous motors
Product specific application
Pumps and fans
Component name
ATS22
Network number of phases
3 phases
[Us] rated supply voltage
230...440 V - 15...10 %
Motor power kW
37 kW 230 V 75 kW 400 V 75 kW 440 V
Factory setting current
131 A
Power dissipation in W
82 W for standard applications
utilisation category
AC-53A
Type of start
Start with torque control (current limited to 3.5 In)
IcL starter rating
140 A for connection in the motor supply line for standard applications
IP degree of protection
IP00
Assembly style
With heat sink
Function available
Internal bypass
Supply voltage limits
195…484 V
Supply frequency
50...60 Hz - 10...10 %
Network frequency
45...66 Hz
device connection
In the motor supply line To the motor delta terminals
[Uc] control circuit voltage
230 V - 15...10 % 50/60 Hz
Control circuit consumption
20 W
Discrete output number
2
Discrete output type
Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Minimum switching current
100 mA at 12 V DC (relay outputs)
Maximum switching current
5 A 250 V AC resistive 1 relay outputs 5 A 30 V DC resistive 1 relay outputs 2 A 250 V AC inductive 0.4 20 ms relay outputs 2 A 30 V DC inductive 7 ms relay outputs
Discrete input number
3
Discrete input type
(LI1, LI2, LI3) logic, 5 mA 4.3 kOhm
Discrete input voltage
24 V <= 30 V
Discrete input logic
Positive logic LI1, LI2, LI3 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA
Output current
0.4...1 Icl adjustable
PTC probe input
750 Ohm
Communication port protocol
Modbus
Connector type
1 RJ45
Communication data link
Serial
Physical interface
RS485 multidrop
Transmission rate
4800, 9600 or 19200 bps
Installed device
31
Protection type
Phase failure: line Thermal protection: motor Thermal protection: starter
Marking
CE
Type of cooling
Forced convection
Operating position
Vertical +/- 10 degree
height
356 mm
Width
150 mm
Depth
229.5 mm
Net weight
18 kg
Motor power range AC-3
30…50 kW at 200…240 V 3 phases 55…100 kW at 380…440 V 3 phases
Motor starter type
Soft starter
Electromagnetic compatibility
Conducted and radiated emissions level A conforming to IEC 60947-4-2 Damped oscillating waves level 3 conforming to IEC 61000-4-12 Electrostatic discharge level 3 conforming to IEC 61000-4-2 Immunity to electrical transients level 4 conforming to IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3 Voltage/current impulse level 3 conforming to IEC 61000-4-5
standards
EN/IEC 60947-4-2
product certifications
UL CSA C-Tick GOST CCC
Vibration resistance
1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-6 1.5 mm (f= 2…13 Hz) conforming to EN/IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
Noise level
56 dB
Pollution degree
Level 2 conforming to IEC 60664-1
Relative humidity
0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
Ambient air temperature for operation
-10…40 °C (without derating) 40…60 °C (with current derating 2.2 % per °C)
Ambient air temperature for storage
-25…70 °C
Operating altitude
<= 1000 m without derating > 1000...< 2000 m with current derating of 2.2 % per additional 100 m
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
25.5 cm
Package 1 Width
32.5 cm
Package 1 Length
41.5 cm
Package 1 Weight
13.207 kg
Unit Type of Package 2
P06
Number of Units in Package 2
4
Package 2 Height
63.0 cm
Package 2 Width
80.0 cm
Package 2 Length
60.0 cm
Package 2 Weight
65.828 kg