ATS22C11S6U

ATS22 SFTSTRTR 110A 600V 110V CI

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

ATS22C11S6U

Information

This Altistart 22 soft starter can feed 3-phase asynchronous motors in supply line connection. It has a rating of 110A, a rated power from 30HP to 100HP and a rated voltage from 230V to 575V AC. It is designed for simple and complex machines such as centrifugal and piston pumps, fans, screw compressors and material handling equipment. Slim form factor improves versatility; allows mounting in frames of any kind of machines. It features an Integrated bypass, this reduces noise and decreases heat dissipation. Compatibility with SoMove software allows configurations and settings to be easily transferred, meaning spares can be quickly installed. It provides smooth starting for your machinery, avoiding mechanical stresses and extending their service life.

Technical Specifications

Range of product

Altistart 22

Product or component type

Soft starter

Product destination

Asynchronous motors

Product specific application

Pumps and fans

Component name

ATS22

Network number of phases

3 phases

[Us] rated supply voltage

208...600 V - 15...10 %

Motor power hp

100 hp 575 V 30 hp 208 V 40 hp 230 V 75 hp 460 V

Factory setting current

96 A

Power dissipation in W

73 W for standard applications

utilisation category

AC-53A

Type of start

Start with torque control (current limited to 3.5 In)

IcL starter rating

110 A for connection in the motor supply line for standard applications

IP degree of protection

IP20

Assembly style

With heat sink

Function available

Internal bypass

Supply voltage limits

177…660 V

Supply frequency

50...60 Hz - 10...10 %

Network frequency

45...66 Hz

device connection

In the motor supply line

[Uc] control circuit voltage

110 V - 15...10 % 50/60 Hz

Control circuit consumption

20 W

Discrete output number

2

Discrete output type

Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O

Minimum switching current

100 mA at 12 V DC (relay outputs)

Maximum switching current

5 A 250 V AC resistive 1 relay outputs 5 A 30 V DC resistive 1 relay outputs 2 A 250 V AC inductive 0.4 20 ms relay outputs 2 A 30 V DC inductive 7 ms relay outputs

Discrete input number

3

Discrete input type

(LI1, LI2, LI3) logic, 5 mA 20 kOhm

Discrete input voltage

110 V <= 121 V

Discrete input logic

Positive logic LI1, LI2, LI3 at State 0: < 20 V and <= 15 mA at State 1: > 79 V, <= 2 mA

Output current

0.4...1 Icl adjustable

PTC probe input

750 Ohm

Communication port protocol

Modbus

Connector type

1 RJ45

Communication data link

Serial

Physical interface

RS485 multidrop

Transmission rate

4800, 9600 or 19200 bps

Installed device

31

Protection type

Phase failure: line Thermal protection: motor Thermal protection: starter

Marking

CE

Type of cooling

Forced convection

Operating position

Vertical +/- 10 degree

height

356 mm

Width

150 mm

Depth

229.5 mm

Net weight

18 kg

Electromagnetic compatibility

Conducted and radiated emissions level A conforming to IEC 60947-4-2 Damped oscillating waves level 3 conforming to IEC 61000-4-12 Electrostatic discharge level 3 conforming to IEC 61000-4-2 Immunity to electrical transients level 4 conforming to IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3 Voltage/current impulse level 3 conforming to IEC 61000-4-5

standards

EN/IEC 60947-4-2

product certifications

CSA UL C-Tick GOST CCC

Vibration resistance

1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-6 1.5 mm (f= 2…13 Hz) conforming to EN/IEC 60068-2-6

Shock resistance

15 gn for 11 ms conforming to EN/IEC 60068-2-27

Noise level

56 dB

Pollution degree

Level 2 conforming to IEC 60664-1

Relative humidity

0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3

Ambient air temperature for operation

-10…40 °C (without derating) 40…60 °C (with current derating 2.2 % per °C)

Ambient air temperature for storage

-25…70 °C

Operating altitude

<= 1000 m without derating > 1000...< 2000 m with current derating of 2.2 % per additional 100 m

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

25.5 cm

Package 1 Width

33.0 cm

Package 1 Length

42.0 cm

Package 1 Weight

13.018 kg

Unit Type of Package 2

P06

Number of Units in Package 2

4

Package 2 Height

75.0 cm

Package 2 Width

80.0 cm

Package 2 Length

60.0 cm

Package 2 Weight

65.072 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet