STBART0200K

ANA IN 2CH RTD/TC/MV KIT

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

STBART0200K

Information

This product is part of the Modicon STB range, an offer of modular distributed I/O. This standard analogue input kit is an accessory kit of Programmable Logic Controllers (PLC) and Programmable Automation Controllers (PAC). It has 2 analogue inputs with 15bit plus sign resolution. This product is compatible with most major fieldbus networks. It is an analogue input kit with a rated supply voltage of 24V DC and a current consumption of 30mA at 5V DC for logic bus. It is an IP20 rated product. It is suitable for packaging, bottling, assembly, distribution, textile, printing and semiconductor machines applications. This product is certified by FM Class 1 Division 2, ATEX category 3G, CE, UL, CSA and C-Tick. This kit is suitable for use with mounting base STBXBA1000 and power distribution module STBPDT3100/3105. The kit includes STBART0200 module, STBXTS1100, 6-terminal screw type connector, STBXBA1000 base and STBXTS2100, 6-terminal spring clamp connector. The Modicon STB distributed I/O solution is an open, modular input/output system that makes it possible to design automation islands managed by a master controller via a bus or communication network.

Technical Specifications

Range of product

Modicon STB distributed I/O solution

Product or component type

Standard analog input kit

Kit composition

STBART0200 module STBXTS1100, 6-terminal screw type connector STBXBA1000 base STBXTS2100, 6-terminal spring clamp connector

Analogue input type

Voltage +/- 80 mV Temperature probe -100...+260 °C Cu 10 2, 3 or 4 wires IEC Temperature probe -100...+450 °C Pt 100 2, 3 or 4 wires US/JIS Temperature probe -100...+450 °C Pt 1000 2, 3 or 4 wires US/JIS Temperature probe -200...+850 °C Pt 100 2, 3 or 4 wires IEC Temperature probe -200...+850 °C Pt 1000 2, 3 or 4 wires IEC Temperature probe -60...+180 °C Ni 100 2, 3 or 4 wires IEC Temperature probe -60...+180 °C Ni 1000 2, 3 or 4 wires IEC Thermocouple +130...+1820 °C thermocouple B Thermocouple -200...+760 °C thermocouple J Thermocouple -270...+1000 °C thermocouple E Thermocouple -270...+1370 °C thermocouple K Thermocouple -270...+400 °C thermocouple T Thermocouple -50...+1665 °C thermocouple R Thermocouple -50...+1665 °C thermocouple S

analogue input number

2

analogue input resolution

15 bits + sign

Type of filter

Single low pass input filter 25 Hz

Absolute maximum input

+/- 7.5 V DC

Cold swapping

Yes

Hot swapping fallback

Yes for standard NIMs

Fallback status

State 0 basic NIMs User configurable standard NIMs

Data format

EN 61131-2 IEC 61131-2

Input impedance

10 MOhm +/- 80 mV

Maximum supply current for sensors

100 mA per input channels

Protection type

Short-circuit protection

Absolute accuracy error

+/- 0.1 % of full scale 25 °C internal +/- 0.15 % of full scale 25 °C external

Insulation between channels and logic bus

1500 V for 1 minute

Addressing requirement

1 word for cold-junction compensation 2 input words

Product compatibility

Mounting base STBXBA1000 Power distribution module STBPDT3100/3105

[Us] rated supply voltage

24 V DC

Supply

Power distribution module

Current consumption

30 mA at 5 V DC for logic bus

Measurement resolution

0.01 mV voltage 0.1 °C or 0.1 °F temperature probe 0.1 °C or 0.1 °F thermocouple

Conversion time

150 ms voltage 60 Hz 170 ms voltage 50 Hz 180 ms temperature probe 60 Hz 2 or 4 wires 200 ms temperature probe 50 Hz 2 or 4 wires 210 ms thermocouple with internal cold-junction compensation 60 Hz 230 ms thermocouple with internal cold-junction compensation 50 Hz 300 ms temperature probe 60 Hz 3 wires 340 ms temperature probe 50 Hz 3 wires 360 ms thermocouple with external cold-junction compensation 60 Hz 400 ms thermocouple with external cold-junction compensation 50 Hz

Maximum wiring resistance

20 Ohm Cu 10 IEC/US/JIS 2 or 3 wires 20 Ohm Ni 100 IEC/US/JIS 2 or 3 wires 20 Ohm Pt 100 IEC/US/JIS 2 or 3 wires 200 Ohm Ni 1000 IEC/US/JIS 2 or 3 wires 200 Ohm Pt 1000 IEC/US/JIS 2 or 3 wires 50 Ohm Cu 10 IEC/US/JIS 4 wires 50 Ohm Ni 100 IEC/US/JIS 4 wires 50 Ohm Pt 100 IEC/US/JIS 4 wires 500 Ohm Ni 1000 IEC/US/JIS 4 wires 500 Ohm Pt 1000 IEC/US/JIS 4 wires

Measurement accuracy

+/- 1 °C Ni 100 25 °C external +/- 1 °C Ni 100 25 °C internal +/- 1 °C Ni 1000 25 °C external +/- 1 °C Ni 1000 25 °C internal +/- 1 °C Pt 100 25 °C internal +/- 1 °C Pt 1000 25 °C internal +/- 1.75 °C thermocouple B with external cold-junction compensation 25 °C +/- 1.75 °C thermocouple E with external cold-junction compensation 25 °C +/- 1.75 °C thermocouple J with external cold-junction compensation 25 °C +/- 1.75 °C thermocouple K with external cold-junction compensation 25 °C +/- 1.75 °C thermocouple R with external cold-junction compensation 25 °C +/- 1.75 °C thermocouple S with external cold-junction compensation 25 °C +/- 1.75 °C thermocouple T with external cold-junction compensation 25 °C +/- 2 °C Pt 100 25 °C external +/- 2 °C Pt 1000 25 °C external +/- 2.85 °C thermocouple B with external cold-junction compensation 60 °C +/- 2.85 °C thermocouple E with external cold-junction compensation 60 °C +/- 2.85 °C thermocouple J with external cold-junction compensation 60 °C +/- 2.85 °C thermocouple K with external cold-junction compensation 60 °C +/- 2.85 °C thermocouple R with external cold-junction compensation 60 °C +/- 2.85 °C thermocouple S with external cold-junction compensation 60 °C +/- 2.85 °C thermocouple T with external cold-junction compensation 60 °C +/- 3.6 °C thermocouple R with internal cold-junction compensation 25 °C +/- 4 °C Cu 10 25 °C external +/- 4 °C Cu 10 25 °C internal +/- 4 °C thermocouple K with internal cold-junction compensation 25 °C +/- 4.1 °C thermocouple S with internal cold-junction compensation 25 °C +/- 4.2 °C thermocouple R with internal cold-junction compensation 60 °C +/- 4.4 °C thermocouple T with internal cold-junction compensation 25 °C +/- 4.6 °C thermocouple B with internal cold-junction compensation 25 °C +/- 4.6 °C thermocouple E with internal cold-junction compensation 25 °C +/- 5 °C thermocouple S with internal cold-junction compensation 60 °C +/- 5.1 °C thermocouple J with internal cold-junction compensation 25 °C +/- 5.5 °C thermocouple K with internal cold-junction compensation 60 °C +/- 6.4 °C thermocouple T with internal cold-junction compensation 60 °C +/- 6.8 °C thermocouple B with internal cold-junction compensation 60 °C +/- 6.8 °C thermocouple E with internal cold-junction compensation 60 °C +/- 7 °C thermocouple J with internal cold-junction compensation 60 °C

Marking

CE

Overvoltage category

II

Status LED

1 LED (green) module status (RDY) 1 LED (red) module error (ERR)

product certifications

UL FM Class 1 Division 2 CSA ATEX Cat 3G C-Tick

Pollution degree

2 conforming to IEC 60664-1

Operating altitude

<= 2000 m

IP degree of protection

IP20 conforming to IEC 61131-2 class 1

Ambient air temperature for operation

32...140 °F without derating

Ambient air temperature for storage

-40...185 °F without derating

Relative humidity

95 % at 60 °C without condensation

Vibration resistance

+/-0.35 mm at 10…58 Hz 3 gn at 58…150 Hz on 35 x 7.5 mm symmetrical DIN rail 5 gn at 58…150 Hz on 35 x 15 mm symmetrical DIN rail

Shock resistance

30 gn for 11 ms conforming to IEC 88 reference 2-27

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

3.000 cm

Package 1 Width

8.300 cm

Package 1 Length

13.300 cm

Package 1 Weight

136.000 g

Unit Type of Package 2

S02

Number of Units in Package 2

42

Package 2 Height

15.000 cm

Package 2 Width

30.000 cm

Package 2 Length

40.000 cm

Package 2 Weight

6.031 kg

Warranty

18 months