140DAM59000

COMB. 115VAC 16IN/8OUT

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

140DAM59000

Technical Specifications

Range of produc

Modicon Quantum automation platform

Product or component type

Mixed discrete I/O module

Discrete I/O number

24

Discrete input number

16 2 groups of 8

Addressing requirement

1 input word 0.5 output word

network frequency limits

47…63 Hz

Discrete input voltage

115 V AC

Input voltage limits

156 V during 10 s 200 V during one cycle 132 V typical

Voltage state 0 guaranteed

0...20 V

Voltage state 1 guaranteed

79...132 V 60 Hz 85...132 V 50 Hz

Current state 0 guaranteed

<= 0.5 mA

Current state 1 guaranteed

<= 11 mA 50 Hz <= 13.2 mA 60 Hz

Input impedance

14400 Ohm capacitive

Response time

4.9...0.75 ms at at state 0 to state 1 7.3...12.3 ms at at state 1 to state 0

Discrete output number

8 2 groups of 4

Discrete output type

Solid state

Discrete output voltage

115 V

Output voltage limits

156 V AC during 10 s 200 V AC during 1 cycle 85...132 V typical AC typical

Minimum load

5 mA

Maximum load current

<= 4 A per point <= 8 A per group <= 8 A per module

Maximum voltage drop

<1.5 V

Absolute maximum output

20 A 2 cycles per point 26 A 3 cycles per group 30 A 1 cycle per point 30 A 2 cycles per group 45 A 1 cycle per group 10 A 3 cycles per point

DV/dt

400 V/µs

Maximum leakage current

2.1 mA 115 V AC input circuit 2 mA output circuit

Response time on output

<= 0.5 ms at state 0 to state 1 <= 0.5 ms at state 1 to state 0

Protection type

On output by RC filter Internal output protection by 5 A fuse per group

Isolation between group

1000 Vrms for 1 minute

Isolation between channels and bus

1780 Vrms for 1 minute

fault indication

Loss of field power on output Blown fuse on output

Power dissipation

5.5 W + (1.1 x total module load current)

External power requirement

85...132 V AC for output circuit

Local signalling

1 LED (green) for bus communication is present (Active) 1 LED (red) for no voltage in output and input (F) 2 LEDs (green) for output is turned on 2 LEDs (red) for fault detected on the input point 2 LEDs (red) for fault detected on the output point

Marking

CE

Bus current requirement

250 mA

Net weight

0.45 kg

Resistance to electrostatic discharge

4 kV contact conforming to IEC 801-2 8 kV on air conforming to IEC 801-2

Resistance to electromagnetic fields

10 V/m 80…1000 MHz conforming to IEC 801-3

ambient air temperature for operation

0…60 °C

Ambient air temperature for storage

-40…85 °C

Relative humidity

95 % without condensation

Operating altitude

<= 5000 m

Standards

FM Class 1 Division 2 UL 508 CSA C22.2 No 142

product certifications

cUL

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

16.3 cm

Package 1 Width

4.5 cm

Package 1 Length

31.2 cm

Package 1 Weight

560.0 g

Unit Type of Package 2

S02

Number of Units in Package 2

2

Package 2 Height

15.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

1.1 kg

Warranty

18 months

Document Links