HDA125U

MCCB h3 x160 TM 3x125A 18kA

Trade Price

£472.81

Per

1

Unit

EA

Pack Quantity

1

HDA125U

Technical Specifications

Number of poles

3 P

Complete device with protection unit

Yes

Trip Unit

TM A/F

Integrated earth fault protection

No

Number of modules

4.5

Rated operational voltage Ue

220 / 415 V

Frequency

50/60 Hz

Rated insulation voltage

690 V

Rated impulse withstand voltage

8 kV

With under voltage release

No

Rated current

125 A

Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2

4 kA

Thermal protection nob setting xIN

0.63 / 0.8 / 1

Breaking capacity on 1 pole for IT 230V NF 60947-2

15 kA

Breaking capacity on 1 pole for IT 400V NF 60947-2

9 kA

Rated service breaking capacity Ics AC according IEC 60947-2

100 %

Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2

25 kA

Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2

25 kA

Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2

18 kA

Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2

18 kA

Rated ultimate short-circuit breaking capacity Icu under 440V AC IEC 60947-2

15 kA

Correction factor of rating current for 2 devices placed side-by-side

1

Correction factor of rating current for 3 devices placed side-by-side

1

Correction factor of rating current for 4 and 5 devices placed side-by-side

1

Correction factor of rating current for 6 devices placed side-by-side

1

Total power loss under IN

33 W

Power loss per pole at In

11 W

Tripmode

TM

Thermal protection trip time

0 ms

Time of response when opening

10 ms

Magnetic trip delay time

0 ms

Electric endurance in number of cycles

1000

Number of mechanical operations

4000

DIN rail mounting with optional adaptator

Yes

Connection cross-sect. rigid cable

4 / 95mm²

Range of the magnetic adjustment

1500 A

Setting type In or Ith

IN

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Motor drive optional

No

Category of use

A

Standard text

IEC 60947-2

European directive WEEE

concerned

Operating temperature

-25…70 °C

Altitude

2000 m

Storage/transport temperature

-35…70 °C

Document Links

Catalogue page

Datasheet