Trade Price
£34.59
Per
1
Unit
EA
Pack Quantity
12
Neutral position
left
Number of protected poles
1
Number of poles
2 P
Curve
C
Concurrently switching N-neutral
Yes
Number of modules
1
Top connection alignement for modular devices
Shifted terminal
Bottom connection alignement for modular devices
Shifted terminal
Rated short circuit breaking capacity Icn AC according IEC60898-1
4.5 kA
Rated operational voltage Ue
230 / 240 V
Type of supply voltage
AC
Frequency
50 to 60 Hz
Rated insulation voltage
500 V
Max operating voltage
253 V
Rated impulse withstand voltage
4000 V
Rated current
16 A
Rated service breaking capacity Ics AC according IEC 60898-1
4.5 kA
min/maxi threshold value of the AC thermal operation
1.13 / 1.45 In
Magnetic regulating currrent
5 / 10 In
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1
4.5 kA
Rating current -25°C
19.7 A
Rating current -20°C
19.4 A
Rating current -15°C
19.1 A
Rating current -10°C
18.8 A
Rating current -5°C
18.5 A
Rating current 0°C
18.1 A
Rating current 5°C
17.8 A
Rating current 10°C
17.5 A
Rating current 15°C
17.1 A
Rating current 20°C
16.7 A
Rating current 25°C
16.4 A
Rating current 30°C
16 A
Rating current 35°C
15.6 A
Rating current 40°C
15.2 A
Rating current 45°C
14.8 A
Rating current 50°C
14.4 A
Rating current 55°C
14 A
Rating current 60°C
13.5 A
Rating current 65°C
13.1 A
Rating current 70°C
12.6 A
Correction factor of rating current for 2 devices placed side-by-side
1
Correction factor of rating current for 3 devices placed side-by-side
0.95
Correction factor of rating current for 4 and 5 devices placed side-by-side
0.9
Correction factor of rating current for 6 devices placed side-by-side
0.85
Correction factor of magnetic tripping with 100 Hz
1.1
Correction factor of magnetic tripping with 200 Hz
1.2
Correction factor of magnetic tripping with 400 Hz
1.5
Correction factor of magnetic tripping with 60 Hz
1
Depth of installed product
70 mm
Height of installed product
84.7 mm
Width of installed product
17.5 mm
Total power loss under IN
4.4 W
Power loss per pole at In
3.1 W
Electric endurance in number of cycles
1000
Number of mechanical operations
20000
Type of top connection for modular devices
with screw
Type of top rail clip for modular devices
Plastic
Type of bottom rail clip for modular devices
metallic
Type of Bottom Connection for modular devices
with screw
Top removability for modular devices
Yes
Bottom removability for modular devices
No
Suitable for flush-mounting
Yes
Connection cross-section at output with screw, for flexible conductor
1 / 16 mm²
Connection cross-section at output with screw, for massive conductor
1 / 25 mm²
Connection cross-section for rigid conductor, upstream terminals with screws
1 / 25 mm²
Connection cross-section of the access with screws, with flexible conductor
1 / 16 mm²
Connection cross-section of input and output with screws, for massive conductors
1 / 25 mm²
Connection cross section of access and exit with screws, for flexible conductor
1 / 16 mm²
Standard text
EN 60898-1
European directive WEEE
concerned
Protection index IP
IP20
Operating temperature
-25…70 °C
Class of energy limitation I²t
3
Altitude
2000 m
Storage/transport temperature
-25…80 °C
Datasheet