Trade Price
£1,621.85
Per
1
Unit
EA
Pack Quantity
1
Number of poles
3 P
Complete device with protection unit
Yes
Trip Unit
LSI
Integrated earth fault protection
No
Number of modules
6
Rated operational voltage Ue
220 / 690 V
Frequency
50/60 Hz
Rated insulation voltage
800 V
Rated impulse withstand voltage
8 kV
With under voltage release
No
Rated current
250 A
Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2
7.5 kA
Thermal protection nob setting xIN
0.4 / 0.5 / 0.63 / 0.8 / 0.9 / 0.95 / 1
Breaking capacity on 1 pole for IT 230V NF 60947-2
60 kA
Breaking capacity on 1 pole for IT 400V NF 60947-2
9 kA
Rated service breaking capacity Ics AC according IEC 60947-2
50 %
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
85 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2
85 kA
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
50 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
50 kA
Rated ultimate short-circuit breaking capacity Icu under 440V AC IEC 60947-2
50 kA
Correction factor of rating current for 2 devices placed side-by-side
1
Correction factor of rating current for 3 devices placed side-by-side
1
Correction factor of rating current for 4 and 5 devices placed side-by-side
1
Correction factor of rating current for 6 devices placed side-by-side
1
Total power loss under IN
73.2 W
Power loss per pole at In
24.4 W
Tripmode
LSI
Thermal protection trip time
5 / 8 / 11 / 21 ms
Time of response when opening
10 ms
Magnetic trip delay time
100 to 200 ms
Electric endurance in number of cycles
1000
Number of mechanical operations
4000
DIN rail mounting with optional adaptator
No
Connection cross-sect. flexible conductor
35 / 150mm²
Type of connection
Terminal
Range of the magnetic adjustment
1400 / 1750 / 2240 / 2800 / 3150 / 3250 / 3250 A
Magnetic protection nob setting xIN
2.5 / 5 / 10
Setting type In or Ith
IrTh
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Yes
Category of use
A
Standard text
IEC 60947-2
European directive WEEE
concerned
Operating temperature
-25…70 °C
Altitude
2000 m
Storage/transport temperature
-35…70 °C
Datasheet