HNC250H

MCCB h250 3P 50kA 250A LSI

Trade Price

£1,621.85

Per

1

Unit

EA

Pack Quantity

1

HNC250H

Technical Specifications

Number of poles

3 P

Complete device with protec­tion unit

Yes

Trip Unit

LSI

Integ­rated earth fault protec­tion

No

Number of modules

6

Rated oper­a­tional voltage Ue

220 / 690 V

Frequency

50/60 Hz

Rated insu­la­tion voltage

800 V

Rated impulse with­stand voltage

8 kV

With under voltage release

No

Rated current

250 A

Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 690V AC IEC 60947-2

7.5 kA

Thermal protec­tion nob setting xIN

0.4 / 0.5 / 0.63 / 0.8 / 0.9 / 0.95 / 1

Breaking capa­city on 1 pole for IT 230V NF 60947-2

60 kA

Breaking capa­city on 1 pole for IT 400V NF 60947-2

9 kA

Rated service breaking capa­city Ics AC according IEC 60947-2

50 %

Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 230V AC IEC 60947-2

85 kA

Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 240V AC IEC 60947-2

85 kA

Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 400V AC IEC 60947-2

50 kA

Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 415V AC IEC 60947-2

50 kA

Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 440V AC IEC 60947-2

50 kA

Correc­tion factor of rating current for 2 devices placed side-by-side

1

Correc­tion factor of rating current for 3 devices placed side-by-side

1

Correc­tion factor of rating current for 4 and 5 devices placed side-by-side

1

Correc­tion factor of rating current for 6 devices placed side-by-side

1

Total power loss under IN

73.2 W

Power loss per pole at In

24.4 W

Trip­mode

LSI

Thermal protec­tion trip time

5 / 8 / 11 / 21 ms

Time of response when opening

10 ms

Magnetic trip delay time

100 to 200 ms

Elec­tric endur­ance in number of cycles

1000

Number of mech­an­ical oper­a­tions

4000

DIN rail mounting with optional adapt­ator

No

Connec­tion cross-sect. flex­ible conductor

35 / 150mm²

Type of connec­tion

Terminal

Range of the magnetic adjust­ment

1400 / 1750 / 2240 / 2800 / 3150 / 3250 / 3250 A

Magnetic protec­tion nob setting xIN

2.5 / 5 / 10

Setting type In or Ith

IrTh

Number of auxil­iary contacts as normally closed contact

0

Number of auxil­iary contacts as normally open contact

0

Number of auxil­iary contacts as change-over contact

0

Motor drive optional

Yes

Category of use

A

Standard text

IEC 60947-2

European directive WEEE

concerned

Oper­ating temper­ature

-25…70 °C

Alti­tude

2000 m

Stor­age/trans­port temper­ature

-35…70 °C

Document Links

Datasheet