HNB100H

MCCB X250 3P 40kA 100A TM

Trade Price

£617.79

Per

1

Unit

EA

Pack Quantity

1

HNB100H

Technical Specifications

Number of poles

3 P

Rated operational voltage Ue

220 / 415 V

Frequency

50/60 Hz

Rated insulation voltage

800 V

Rated impulse withstand voltage

8 kV

Total power loss under IN

24.8 W

Electric endurance in number of cycles

1000

Number of mechanical operations

4000

Connection cross-sect. flexible conductor

35 / 150mm²

Type of connection

Terminal

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

European directive WEEE

concerned

Protection index IP

IP4X

Operating temperature

-25…70 °C

Document Links