HNA063U

MCCB h3 x160 TM 3x63A 40kA

Trade Price

£443.80

Per

1

Unit

EA

Pack Quantity

1

HNA063U

Technical Specifications

Number of poles

3 P

Complete device with protec­tion unit

Yes

Trip Unit

TM A/F

Integ­rated earth fault protec­tion

No

Number of modules

4.5

Rated oper­a­tional voltage Ue

220 / 415 V

Frequency

50/60 Hz

Rated insu­la­tion voltage

690 V

Rated impulse with­stand voltage

8 kV

With under voltage release

No

Rated current

63 A

Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 690V AC IEC 60947-2

6 kA

Thermal protec­tion nob setting xIN

0.63 / 0.8 / 1

Breaking capa­city on 1 pole for IT 230V NF 60947-2

51 kA

Breaking capa­city on 1 pole for IT 400V NF 60947-2

9 kA

Rated service breaking capa­city Ics AC according IEC 60947-2

50 %

Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 230V AC IEC 60947-2

85 kA

Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 240V AC IEC 60947-2

85 kA

Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 400V AC IEC 60947-2

40 kA

Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 415V AC IEC 60947-2

40 kA

Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 440V AC IEC 60947-2

25 kA

Correc­tion factor of rating current for 2 devices placed side-by-side

1

Correc­tion factor of rating current for 3 devices placed side-by-side

1

Correc­tion factor of rating current for 4 and 5 devices placed side-by-side

1

Correc­tion factor of rating current for 6 devices placed side-by-side

1

Total power loss under IN

30 W

Power loss per pole at In

10 W

Trip­mode

TM

Thermal protec­tion trip time

0 ms

Time of response when opening

10 ms

Magnetic trip delay time

0 ms

Elec­tric endur­ance in number of cycles

1000

Number of mech­an­ical oper­a­tions

4000

DIN rail mounting with optional adapt­ator

Yes

Connec­tion cross-sect. rigid cable

4 / 95mm²

Type of connec­tion

with screw

Range of the magnetic adjust­ment

1000 A

Setting type In or Ith

IN

Number of auxil­iary contacts as normally closed contact

0

Number of auxil­iary contacts as normally open contact

0

Number of auxil­iary contacts as change-over contact

0

Motor drive optional

No

European directive WEEE

not concerned

Protec­tion index IP

IP4X

Alti­tude

2000 m

Air humidity protec­tion

for all climates

Document Links

Datasheet