ESC465

Contactor 63A, 2NO+2NC, 230V

Trade Price

£281.24

Per

1

Unit

EA

Pack Quantity

4

ESC465

Technical Specifications

Number of poles

4 P

Number of modules

3

Rated oper­a­tional voltage Ue

400 V

Frequency

50 Hz

Rated insu­la­tion voltage

440 V

DC control voltage

0 V

Command voltage AC

230 V

Rated impulse with­stand voltage

4 kV

Rated current

63 A

Thermal rated current outside of hous­ings

63 A

Accept­able current load with AC7 category A

63 A

Accept­able current load with AC7 category B

32 A

Depth of installed product

60 mm

Height of installed product

85 mm

Width of installed product

54 mm

Inrush power absorbed

62.5 VA

Oper­ating consump­tion

5.7 VA

Total power loss under IN

11.5 W

Power loss per contact

5 W

Power dissip­a­tion per coil

1.5 W

Contact rating with 230 V in AC7 category A

11.6 kW

Contact rating with 230 V in AC7 category B

3.3 kW

Contact rating with 400 V in AC7 category A

35 kW

Contact rating with 400 V in AC7 category B

7.8 kW

Time of response when opening

20 ms

Time of response when closing

25 ms

Winding resist­ance

770 Ω

Elec­tric endur­ance in number of cycles

30000

Number of mech­an­ical oper­a­tions

1000000

Max. power with fluor­es­cent parallel lamps

2100 VA

Fluor­es­cent lamps in duo circuit

4700 VA

Max. load fluor­es­cent lamp

3000 VA

Max. power with incan­des­cent lamps

6500 W

Connec­tion cross-sect. flex­ible conductor

1,5 / 16mm²

Number of contacts

4

Type of connec­tion

with screw

Connec­tion cross-sec­tion of the control cable solid

1 / 2.5 mm²

Can be access­or­ized

Yes

Local oper­a­tion/hand oper­a­tion

No

European directive WEEE

concerned

Protec­tion index IP

IP2X

Protec­tion class

isol.­class II

Oper­ating temper­ature

-10…50 °C

Stor­age/trans­port temper­ature

-40…80 °C

Document Links