HCS161AC

SWITCH h3+ P160 4x160A

Trade Price

£417.37

Per

1

Unit

EA

Pack Quantity

1

HCS161AC

Technical Specifications

Neutral position

left

Number of poles

4 P

Type of pole

4 P

Fixing mode

fixing plate

Type of case

Fixed built-in

Reversing switch

No

Version as main switch

Yes

Version as emergency stop installation

Yes

Version as safety switch

No

Version as maintenance-/service switch

Yes

Trip Unit

SWITCH

Concurrently switching N-neutral

Yes

Motor drive integrated

No

Rated operational voltage Ue

220 / 690 V

Type of supply voltage

AC

Frequency

50 to 60 Hz

Rated insulation voltage

800 V

Rated impulse withstand voltage

8 kV

Rated current

160 A

Rated short-time withstand current Icw

2 kA

Rated short-time withstand current Icw t=1s 660-690 V AC according IEC 60947-3

2 kA

Rated short-time withstand current Icw t=1s 220-240 V AC according IEC 60947-3

2 kA

Rated short-time withstand current Icw t=1s 380-415 V AC according IEC 60947-3

2 kA

Rated operational current in AC21

160 A

Depth of installed product

97 mm

Height of installed product

130 mm

Width of installed product

120 mm

Total power loss under IN

42.3 W

Power loss per pole at In

14.1 W

Electric endurance in number of cycles

10000

Number of mechanical operations

40000

Interlockable

Yes

Toggle colour

Grey

Tightening torque

6Nm

DIN rail mounting with optional adaptator

Yes

Suitable for front mounting center

No

Suitable for front mounting

No

Suitable for ground mounting

Yes

Connection cross-sect. rigid cable

6 / 95mm²

Type of connection

with screw

Cable Material

Cu

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Motor drive optional

No

Can be accessorized

Yes

Vibrations and shocks withstand

IEC 68068-2-52 Test FC

European directive WEEE

concerned

Protection index IP

IP4X

Degree of pollution according to IEC 60664 / IEC 60947-2

3

Altitude

2000 m

Temp.-rise limits for access. parts (toggle) according to product standard

25 K

Temp.-rise limits for access. parts (not touched) according to product standard

50 K

Temp.rise limits for access. parts (to be touched) according to product standard

40 K

Temperature-rise limits for terminals according to the product standard

65 K

Document Links

Datasheet