Trade Price
£341.37
Per
1
Unit
EA
Pack Quantity
1
Neutral position
left
Number of protected poles
4
Number of poles
4 P
Fixing mode
fixing plate
Type of case
Fixed built-in
Complete device with protection unit
Yes
Reversing switch
No
Version as main switch
Yes
Version as emergency stop installation
No
Version as safety switch
No
Version as maintenance-/service switch
Yes
Trip Unit
TM A/A
Integrated earth fault protection
No
Concurrently switching N-neutral
Yes
Motor drive integrated
No
Rated operational voltage Ue
220 / 690 V
Type of supply voltage
AC
Frequency
50 to 60 Hz
Rated insulation voltage
800 V
Rated impulse withstand voltage
8 kV
With under voltage release
No
Rated current
40 A
Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2
6 kA
Thermal protection nob setting xIN
0.63 / 0.8 / 1
Rating current 10°C according to IEC 60947
49.9 A
Rating current 150°C according to IEC 60947
48.8 A
Rating current 20°C according to IEC 60947
47.6 A
Rating current 25°C according to IEC 60947
46.5 A
Rating current 30°C according to IEC 60947
45.2 A
Rating current 35°C according to IEC 60947
44 A
Rating current 40°C according to IEC 60947
42.7 A
Rating current 45°C according to IEC 60947
41.4 A
Rating current 50°C according to IEC 60947
40 A
Rating current 55°C according to IEC 60947
38.6 A
Rating current 60°C according to IEC 60947
37.1 A
Rating current 65°C according to IEC 60947
35.6 A
Rating current 70°C according to IEC 60947
34 A
Rated service breaking capacity Ics under 660V AC according IEC 60947-2
6 kA
Breaking capacity on 1 pole for IT 230V NF 60947-2
6 kA
Breaking capacity on 1 pole for IT 400V NF 60947-2
6 kA
Breaking capacity on 1 pole for IT 415V NF 60947-2
6 kA
Breaking capacity on 1 pole for IT 690V NF 60947-2
2.5 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
85 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2
85 kA
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
70 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
70 kA
Range of the thermal adjustment
25 / 32 / 40 A
Rated service breaking capacity Ics under 110-138V AC according IEC 60947-2
85 kA
Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2
85 kA
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2
70 kA
Rated ultimate short-circuit breaking capacity Icu under 660V AC IEC 60947-2
6 kA
Depth of installed product
97 mm
Height of installed product
130 mm
Width of installed product
120 mm
Power loss per pole at 0.63*In
3.46 W
Power loss per pole at 0.8*In
5.68 W
Total power loss at 0.63*In
10.39 W
Total power loss at 0.8*In
17.03 W
Total power loss under IN
27.9 W
Power loss per pole at In
9.3 W
Short-time delayed tripping
No
Electric endurance in number of cycles
10000
Number of mechanical operations
40000
Interlockable
Yes
Tightening torque
6Nm
DIN rail mounting with optional adaptator
Yes
Suitable for front mounting center
No
Suitable for front mounting
No
Suitable for ground mounting
Yes
Connection cross-sect. rigid cable
6 / 95mm²
Type of connection
with screw
Instantaneous protection (Ii): type
fixed
Cable Material
Cu
Range of the magnetic adjustment
240 / 320 / 400 / 480 A
Magnetic protection nob setting xIN
6 / 8 / 10 / 12
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Motor drive optional
No
Can be accessorized
Yes
Vibrations and shocks withstand
IEC 68068-2-52 Test FC
European directive WEEE
concerned
Protection index IP
IP4X
Degree of pollution according to IEC 60664 / IEC 60947-2
3
Altitude
2000 m
Temperature of calibration
50 °C
Datasheet