Trade Price
£1,166.53
Per
1
Unit
EA
Pack Quantity
1
Neutral position
without neutral
Number of protected poles
3
Number of poles
3 P
Fixing mode
fixing plate
Type of case
Fixed built-in
Complete device with protection unit
Yes
Version as main switch
Yes
Version as emergency stop installation
No
Version as safety switch
No
Version as maintenance-/service switch
Yes
Trip Unit
LSI
Integrated earth fault protection
No
Motor drive integrated
No
Rated operational voltage Ue
220 / 690 V
Type of supply voltage
AC
Frequency
50 to 60 Hz
Rated insulation voltage
800 V
Rated impulse withstand voltage
8 kV
With under voltage release
No
Rated current
250 A
Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2
12 kA
Rating current 10°C according to IEC 60947
250 A
Rating current 150°C according to IEC 60947
250 A
Rating current 20°C according to IEC 60947
250 A
Rating current 25°C according to IEC 60947
250 A
Rating current 30°C according to IEC 60947
250 A
Rating current 35°C according to IEC 60947
250 A
Rating current 40°C according to IEC 60947
250 A
Rating current 45°C according to IEC 60947
250 A
Rating current 50°C according to IEC 60947
250 A
Rating current 55°C according to IEC 60947
250 A
Rating current 60°C according to IEC 60947
250 A
Rating current 65°C according to IEC 60947
250 A
Rating current 70°C according to IEC 60947
250 A
Rated service breaking capacity Ics under 660V AC according IEC 60947-2
12 kA
Breaking capacity on 1 pole for IT 230V NF 60947-2
10 kA
Breaking capacity on 1 pole for IT 400V NF 60947-2
10 kA
Breaking capacity on 1 pole for IT 415V NF 60947-2
10 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
100 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2
100 kA
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
70 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
70 kA
Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2
100 kA
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2
70 kA
Rated ultimate short-circuit breaking capacity Icu under 660V AC IEC 60947-2
12 kA
Depth of installed product
150 mm
Height of installed product
260 mm
Width of installed product
140 mm
Power loss per pole at 0.63*In
4.9 W
Power loss per pole at 0.8*In
7.8 W
Total power loss at 0.63*In
14.7 W
Total power loss at 0.8*In
23.5 W
Total power loss under IN
36.8 W
Power loss per pole at In
12.3 W
Time of response when opening
10 ms
DIN rail mounting with optional adaptator
No
Suitable for front mounting
No
Suitable for ground mounting
Yes
Type of connection
Terminal
Cable Material
Cu
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Yes
Can be accessorized
Yes
European directive WEEE
concerned
Protection index IP
IP4X
Degree of pollution according to IEC 60664 / IEC 60947-2
3
Altitude
2000 m
Temperature of calibration
50 °C
Datasheet