MB125A

MCB 1P 6kA B-25A 1M

Trade Price

£22.65

Per

1

Unit

EA

Pack Quantity

12

MB125A

Technical Specifications

Number of protected poles

1

Number of poles

1 P

Type of pole

1 P

Curve

B

Concurrently switching N-neutral

No

Number of modules

1

Top connection alignement for modular devices

Aligned terminal

Bottom connection alignement for modular devices

Aligned terminal

Rated short circuit breaking capacity Icn AC according IEC60898-1

6 kA

Rated operational voltage Ue

230 / 400 V

Type of supply voltage

AC

Frequency

50 to 60 Hz

Rated insulation voltage

500 V

Rated impulse withstand voltage

4000 V

Rated current

25 A

Rated service breaking capacity Ics AC according IEC 60898-1

6 kA

min/maxi threshold value of the AC thermal operation

1.13 / 1.45 In

Magnetic regulating currrent

3 / 5 In

min/maxi threshold value of the DC magnetic operation

3 / 7.5 In

min/maxi threshold value of the DC thermal operation

1.13 / 1.45 In

Breaking capacity on 1 pole for IT 400V NF 60947-2

3 kA

Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1

6 kA

Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2

10 kA

Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2

10 kA

Rating current -25°C

32.2 A

Rating current -20°C

31.6 A

Rating current -15°C

31 A

Rating current -10°C

30.4 A

Rating current -5°C

29.8 A

Rating current 0°C

29.1 A

Rating current 5°C

28.5 A

Rating current 10°C

27.8 A

Rating current 15°C

27.1 A

Rating current 20°C

26.4 A

Rating current 25°C

25.7 A

Rating current 30°C

25 A

Rating current 35°C

24.2 A

Rating current 40°C

23.5 A

Rating current 45°C

22.7 A

Rating current 50°C

21.8 A

Rating current 55°C

21 A

Rating current 60°C

20 A

Rating current 65°C

19.3 A

Rating current 70°C

18.4 A

Correction factor of rating current for 2 devices placed side-by-side

1

Correction factor of rating current for 3 devices placed side-by-side

0.95

Correction factor of rating current for 4 and 5 devices placed side-by-side

0.9

Correction factor of rating current for 6 devices placed side-by-side

0.85

Correction factor of magnetic tripping with 100 Hz

1.1

Correction factor of magnetic tripping with 200 Hz

1.2

Correction factor of magnetic tripping with 400 Hz

1.5

Correction factor of magnetic tripping with 60 Hz

1

Depth of installed product

70 mm

Height of installed product

83 mm

Width of installed product

17.5 mm

Total power loss under IN

3 W

Power loss per pole at In

3 W

Electric endurance in number of cycles

10000

Number of mechanical operations

20000

Type of top connection for modular devices

with screw

Tightening torque

2,8Nm

Type of top rail clip for modular devices

NA

Type of bottom rail clip for modular devices

metallic

Type of Bottom Connection for modular devices

BIconnect

Top removability for modular devices

No

Bottom removability for modular devices

No

Connection cross-section of input and output with screws, for massive conductors

1 / 35 mm²

Connection cross section of access and exit with screws, for flexible conductor

1 / 25 mm²

Type of connection

with screw

Standard text

EN 60898-1

European directive WEEE

concerned

Protection index IP

IP20

Operating temperature

-25…70 °C

Degree of pollution according to IEC 60664 / IEC 60947-2

2

Class of energy limitation I²t

3

Altitude

2000 m

Air humidity protection

for all climates

Storage/transport temperature

-25…80 °C

Document Links

Datasheet