HES041JC

MCCB h3+ P160 LSI 4x40A 70kA

Trade Price

£662.70

Per

1

Unit

EA

Pack Quantity

1

HES041JC

Technical Specifications

Neutral position

left

Number of protected poles

4

Number of poles

4 P

Fixing mode

fixing plate

Type of case

Fixed built-in

Complete device with protection unit

Yes

Reversing switch

No

Version as main switch

Yes

Version as emergency stop installation

No

Version as safety switch

No

Version as maintenance-/service switch

Yes

Trip Unit

LSI

Integrated earth fault protection

No

Concurrently switching N-neutral

Yes

Motor drive integrated

No

Rated operational voltage Ue

220 / 690 V

Type of supply voltage

AC

Frequency

50 to 60 Hz

Rated insulation voltage

800 V

Rated impulse withstand voltage

8 kV

With under voltage release

No

Rated current

40 A

Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2

6 kA

Rated short-time withstand current Icw t=0.4S 220-240 V AC according IEC 60947-2

1.6 kA

Rated short-time withstand current Icw t=0.4S 380-415 V AC according IEC 60947-2

1.6 kA

Rated short-time withstand current Icw t=0.4S 660-690 V AC according IEC 60947-2

1.6 kA

Rating current 10°C according to IEC 60947

40 A

Rating current 150°C according to IEC 60947

40 A

Rating current 20°C according to IEC 60947

40 A

Rating current 25°C according to IEC 60947

40 A

Rating current 30°C according to IEC 60947

40 A

Rating current 35°C according to IEC 60947

40 A

Rating current 40°C according to IEC 60947

40 A

Rating current 45°C according to IEC 60947

40 A

Rating current 50°C according to IEC 60947

40 A

Rating current 55°C according to IEC 60947

40 A

Rating current 60°C according to IEC 60947

40 A

Rating current 65°C according to IEC 60947

40 A

Rating current 70°C according to IEC 60947

40 A

Rated service breaking capacity Ics under 660V AC according IEC 60947-2

6 kA

Breaking capacity on 1 pole for IT 230V NF 60947-2

2.5 kA

Breaking capacity on 1 pole for IT 400V NF 60947-2

2.5 kA

Breaking capacity on 1 pole for IT 415V NF 60947-2

2.5 kA

Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2

85 kA

Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2

85 kA

Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2

70 kA

Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2

70 kA

Rated service breaking capacity Ics under 110-138V AC according IEC 60947-2

85 kA

Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2

85 kA

Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2

70 kA

Rated ultimate short-circuit breaking capacity Icu under 660V AC IEC 60947-2

6 kA

Depth of installed product

97 mm

Height of installed product

130 mm

Width of installed product

120 mm

Total power loss under IN

1.68 W

Power loss per pole at In

0.56 W

Electric endurance in number of cycles

10000

Number of mechanical operations

40000

Interlockable

Yes

Tightening torque

6Nm

DIN rail mounting with optional adaptator

Yes

Suitable for front mounting center

No

Suitable for front mounting

No

Suitable for ground mounting

Yes

Connection cross-sect. rigid cable

6 / 95mm²

Type of connection

with screw

Instantaneous protection (Ii): type

adjustable

Cable Material

Cu

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Motor drive optional

No

Can be accessorized

Yes

Vibrations and shocks withstand

IEC 68068-2-52 Test FC

European directive WEEE

concerned

Protection index IP

IP4X

Degree of pollution according to IEC 60664 / IEC 60947-2

3

Altitude

2000 m

Temperature of calibration

50 °C

Document Links

Datasheet