58000-600APO

Apollo Discovery Optical Smoke Detector

Trade Price

£65.09

Per

1

Unit

EACH

Pack Quantity

58000-600APO

Information

A high specification programmable opticial smoke detector with drift compensation. Fully compatible with C-TEC’s XFP & ZFP XP95/Discovery Addressable Fire Panels. User programmable to operate in one of five sensivity modes (e.g. Mode 1 will give a higher senstivity to fire than Mode 5). Works using the light scatter principle and responds well to slow-burning, smouldering fires. Remote test feature. Red LED illuminates when the detector is in alarm. Certified to EN54-7 by the LPCB. Requires a 45681-210APO standard base or 45681-242APO low power relay base. ‘Xpert’ card addressed for speedy installation.

Technical Specifications

Approvals/certifications

Certified to EN54-7 by the LPCB.

Compatibility

Compatible with C-TEC's XFP/ZFP XP95/Discovery Addressable Fire Panels.

Application/operation

Generates an alarm when it detects a pre-set threshold of smoke penetration in its smoke chamber. Provides a very good response to overheating/thermal combustion and a good response to smouldering/

Application temperature

n/a

Static response temperature

n/a

Sensitivity

Option to select 5 different operating modes at the fire panel. See Operation Modes tab below for details.

Supply wiring

2-wire, polarity insensitive.

Supply/operating voltage

17 to 28V DC.

Quiescent current

440µA.

Alarm current

3.4mA (LED illuminated).

Indicators

2 clear LEDs emitting red light when in alarm. Optional remote LED.

Connections

L1&L2 supply in/out; +R remote LED +Ve connection; -R remote LED -Ve connection. (5mA max. remote LED current @ 5V measured across remote load).

Product dimensions (mm)

100mm diameter x 42 mm H (not in base). 50mm height when in base.

Construction & finish

White polycarbonate UL94-VO. Nickel plated stainless steel terminals.

IP Rating

IP44.

Weight

105g (not in base); 160g (in base).

Operating conditions/temperature

-40ºC to +70ºC.

Notes

Requires a BF308XP standard base or BF308XPR low power relay base. 1mA power up surge current for 0.3 seconds.

Mode

Alarm Threshold (%/m)

1

1.4

2

1.4

3

2.1

4

2.1

5

2.4

Document Links

Datasheet