58000-400APO

Apollo Discovery Heat Detector

Trade Price

£65.09

Per

1

Unit

EACH

Pack Quantity

58000-400APO

Information

A high specification programmable heat detector. Fully compatible with C-TEC’s XFP & ZFP XP95/Discovery Addressable Fire Panels. User programmable to operate in one of five sensivity modes (e.g. Mode 1 will give a higher senstivity to fire than Mode 5). Uses a single thermistor to sense the air at the detector position. Ideal in environments that are dirty or smoky under normal conditions such as warehouses, loading bays and car parks. Remote test feature. Red LED illuminates when the detector is in alarm. Certified to EN54-5 by the LPCB. Requires a 45681-210APO standard base or 45681-242APO low power relay base. ‘Xpert’ card addressed for speedy installation.

Technical Specifications

Approvals/certifications

Certified to EN54-5 by the LPCB.

Compatibility

Compatible with C-TEC's XFP/ZFP XP95/Discovery Addressable Fire Panels.

Application/operation

Uses a single thermistor to sense the air temperature at the detector position. Provides a very good response in environments that are dirty or smoky in normal conditions.

Application temperature

n/a

Static response temperature

n/a

Sensitivity

Option to select 5 different operating modes at the fire panel. See Operation Modes tab below for details.

Supply wiring

2-wire, polarity insensitive.

Supply/operating voltage

17 to 28V DC.

Quiescent current

350µA.

Alarm current

3.4mA (LED illuminated).

Indicators

2 clear LEDs emitting red light when in alarm. Optional remote LED.

Connections

L1&L2 supply in/out; +R remote LED +Ve connection; -R remote LED -Ve connection. (5mA max. remote LED current @ 5V measured across remote load).

Product dimensions (mm)

100mm diameter x 42 mm H (not in base). 50mm height when in base.

Construction & finish

White polycarbonate UL94-VO. Nickel plated stainless steel terminals.

IP Rating

IP44.

Weight

105g (not in base); 160g (in base).

Operating conditions/temperature

-40ºC to +80ºC.

Notes

Requires a BF308XP standard base or BF308XPR low power relay base. 1mA power up surge current for 0.3 seconds.

Document Links

Datasheet