Trade Price
£57.00
Per
1
Unit
EACH
Pack Quantity
Fully compatible with C-TEC’s XFP & ZFP XP95/Discovery Addressable Fire Panels. Works using the light scatter principle. Responds well to slow-burning, smouldering fires. Well-suited for bedrooms and escape routes. Red LED illuminates when the detector is in alarm. Certified to EN54-7 by the LPCB. Requires a 45681-210APO standard base or 45681-242APO low power relay base. ‘Xpert’ card addressed for speedy installation.
Approvals/certifications
Certified to EN54-7 by the LPCB.
Compatibility
Compatible with C-TEC's XFP/ZFP XP95/Discovery Addressable Fire Panels.
Application/operation
Generates an alarm when it detects a pre-set threshold of smoke penetration in its smoke chamber. Provides a very good response to overheating/thermal combustion and a good response to smouldering/
Application temperature
n/a
Static response temperature
n/a
Sensitivity
Nominal alarm threshold of 2.4% light grey smoke obscuration per metre.
Supply wiring
2-wire, polarity insensitive.
Supply/operating voltage
17 to 28V DC.
Quiescent current
340µA average; 600µA peak.
Alarm current
2mA (LED illuminated).
Indicators
Clear LED emitting red light when in alarm.
Connections
L1&L2 supply in/out; +R remote LED +Ve connection; -R remote LED -Ve connection. (4mA remote LED current @ 5V measured across remote load).
Product dimensions (mm)
100mm diameter x 42 mm H (not in base). 50mm height when in base.
Construction & finish
White polycarbonate V.O rated rated to UL94. Stainless steel terminals.
IP Rating
IP43.
Weight
105g (not in base); 157g (in base).
Operating conditions/temperature
-20ºC to +60ºC.
Notes
Requires a BF308XP standard base or BF308XPR low power relay base. 1mA power up surge current for 0.3 seconds.