PSM measurement modules with switching functions for outputs and energy measurement. Versions with IEC 60320 C13 & C19 slots and CEE 7/3 (earthing contact socket) available. A power meter and switching functions for the output slots can be added to any PSM busbar with these PSM plug-in modules. The modules are also suitable for upgrading existing PSM installations if it becomes necessary to record the power data or add a switching option for the connected equipment. There are three variants available with different socket types. In the PSM busbar, the PSM modules occupy two module slots each. Measurements are displayed locally on a backlit LC display. For quick checks, the colour changes to red if current and power limits are exceeded. DK PSM measuring module, for modular PSM power distribution. Occupies 2 slots in the busbar. Output: IEC 60 320 4 x C19, 2 x C13, input: 207 V – 250 V, 16 A, (max. 3680 W)
Article number:
DK 7859.420
Benefits
Simple, shock-hazard-protected, plug & play installation with the system operational
Function principle
Measurement of power consumption per module
Material
Socket inserts: Plastic (PA6 GF 30 V1)
Section: Aluminium, anodised
Supply includes
PSM measurement modules with CAN bus
CAN bus connection cable, 1 m
Distribution output per module
3,680 W
Switching load per relay
4,000 VA
Length
500 mm
Contamination level
2
Interface bus system
2 x CAN bus interfaces to CMC III (max. 16 on PU/4 on PU Compact)
Qty.
1
Relay version
Dual coil, bistable
Rated operating voltage
18 V (DC) - 24 V (DC), power supply via CMC III system
Input voltage
230 V AC
Tolerance of input voltage
± 10 %
Rated current
16 A
Required number of module slots
2
No. of participating PU compact (max.)
4
No. of participating PU (max.)
8
Directives
Low Voltage Directive 2014/35/EU
IP protection category to IEC 60 529
IP 20
Monitoring
Alarm management via CMC III (e.g. e-mail or text message)
Standards
EN 50 600-2-2
Measurement functions, description
Voltage V, current A, frequency Hz
Protocols
Network functionality (only in conjunction with CMC III system): IPv4, IPv6, SNMPv3, Modbus/TCP, OPC-UA
Dimensions
Width: 53 mm
Depth: 45 mm
Length: 500 mm
Maximum operating altitude
2,000 m
Operating temperature range
5 °C...60 °C
Ambient humidity (non-condensing)
90 %
Sockets
2 x C13 / 4 x C19
Relative humidity (non-condensing)
10 %
Storage temperature range
-20 °C...70 °C
Packs of
1 pc(s).
Weight/pack
0.992 kg
Customs tariff number
85369001
EAN
4028177801851
ETIM 7.0
EC000330
ECLASS 8.0
27371306