7859420

PSM 4XC19 MEASURING/SWITCHABLE (+ 2XC13) CMC III / CAN 16A / 1P

Trade Price

£716.26

Per

1

Unit

EACH

Pack Quantity

1

7859420

Information

PSM measurement modules with switching functions for outputs and energy measurement. Versions with IEC 60320 C13 & C19 slots and CEE 7/3 (earthing contact socket) available. A power meter and switching functions for the output slots can be added to any PSM busbar with these PSM plug-in modules. The modules are also suitable for upgrading existing PSM installations if it becomes necessary to record the power data or add a switching option for the connected equipment. There are three variants available with different socket types. In the PSM busbar, the PSM modules occupy two module slots each. Measurements are displayed locally on a backlit LC display. For quick checks, the colour changes to red if current and power limits are exceeded. DK PSM measuring module, for modular PSM power distribution. Occupies 2 slots in the busbar. Output: IEC 60 320 4 x C19, 2 x C13, input: 207 V – 250 V, 16 A, (max. 3680 W)

Technical Specifications

Article number:

DK 7859.420

Benefits

Simple, shock-hazard-protected, plug & play installation with the system operational

Function principle

Measurement of power consumption per module

Material

Socket inserts: Plastic (PA6 GF 30 V1)

Section: Aluminium, anodised

Supply includes

PSM measurement modules with CAN bus

CAN bus connection cable, 1 m

Distribution output per module

3,680 W

Switching load per relay

4,000 VA

Length

500 mm

Contamination level

2

Interface bus system

2 x CAN bus interfaces to CMC III (max. 16 on PU/4 on PU Compact)

Qty.

1

Relay version

Dual coil, bistable

Rated operating voltage

18 V (DC) - 24 V (DC), power supply via CMC III system

Input voltage

230 V AC

Tolerance of input voltage

± 10 %

Rated current

16 A

Required number of module slots

2

No. of participating PU compact (max.)

4

No. of participating PU (max.)

8

Directives

Low Voltage Directive 2014/35/EU

IP protection category to IEC 60 529

IP 20

Monitoring

Alarm management via CMC III (e.g. e-mail or text message)

Standards

EN 50 600-2-2

Measurement functions, description

Voltage V, current A, frequency Hz

Protocols

Network functionality (only in conjunction with CMC III system): IPv4, IPv6, SNMPv3, Modbus/TCP, OPC-UA

Dimensions

Width: 53 mm

Depth: 45 mm

Length: 500 mm

Maximum operating altitude

2,000 m

Operating temperature range

5 °C...60 °C

Ambient humidity (non-condensing)

90 %

Sockets

2 x C13 / 4 x C19

Relative humidity (non-condensing)

10 %

Storage temperature range

-20 °C...70 °C

Packs of

1 pc(s).

Weight/pack

0.992 kg

Customs tariff number

85369001

EAN

4028177801851

ETIM 7.0

EC000330

ECLASS 8.0

27371306

Document Links

Datasheet