Trade Price
£566.17
Per
1
Unit
EACH
Pack Quantity
1
The new generation of roof-mounted fans is one system for all sizes: only one mounting cut-out is needed for all output categories. Air routing with minimal pressure losses ensures a high level of efficiency, while an innovative clamping attachment supports a high protection category of IP54. Roof-mounted fan with a high protection category and flexible installation from the inside or outside. SK Roof-mounted fan TopTherm, 863/942 m³/h, 400-460 V, 3~, 50/60 Hz, WHD: 400 x 133 x 400 mm
Article number:
SK 3140.140
Colour
RAL 7035
Supply includes
Complete unit ready to install, including pleated filter
Fan
Radial, rotary current motor
Air throughput, unimpeded airflow (with pleated filter)
At 50 Hz: 800 m³/h
At 60 Hz: 853 m³/h
Air throughput, unimpeded air flow (without filter mats)
At 50 Hz: 863 m³/h
At 60 Hz: 942 m³/h
Rated operating voltage
380 V - 415 V, 3~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 98 W
At 60 Hz: 130 W
Rated current max.
At 50 Hz: 0.17 A
At 60 Hz: 0.2 A
Dimensions
Width: 400 mm
Height: 133 mm
Depth: 400 mm
Mounting cut-out
Cut-out width: 258 mm
Cut-out depth: 258 mm
Installation depth
34.6 mm
IP protection category to IEC 60 529
IP 21 without filter mat
Protection category NEMA
NEMA 12
Note
A chopped-fibre filter filter may optionally be used to increase the protection category to IP55 (see accessories).
Service life of fans (L10, 40 °C)
At 50 Hz: 63,500 h
At 60 Hz: 61,500 h
Operating temperature range
-20 °C...55 °C
Storage temperature range
-40 °C...70 °C
Noise level
At 50 Hz: 56 dB(A)
At 60 Hz: 58 dB(A)
Packs of
1 pc(s).
Weight/pack
6 kg
Customs tariff number
84145915
EAN
4028177709133
ETIM 7.0
EC000320
ECLASS 8.0
27180716